Chapter 4 Explanation of Functions

(3) Free V/f characteristic setting

The free V/f characteristic setting function allows you to set an arbitrary V/f characteristic by specifying the voltages and frequencies (b100 to b113) for the seven points on the V/f characteristic curve.

The free V/f frequencies (1 to 7) set by this function must always be in the collating sequence of "1 ≤ 2 ≤ 3

4 ≤ 5 ≤ 6 ≤ 7".

Since all free V/f frequencies are set to 0 Hz as default (factory setting), specify their arbitrary values (begin setting with free-setting V/f frequency (7)). (The inverter cannot operate with the free V/f characteristic in the factory setting.)

Enabling the free V/f characteristic setting function disables the torque boost selection (A041/A241), base frequency setting (A003/A203/A303), and maximum frequency setting (A004/A204/A304). (The inverter assumes the value of free-setting V/f frequency (7) as the maximum frequency.)

Item

Function code

Data

Description

Free-setting V/f frequency (7)

b112

0.to 400.(Hz)

 

Free-setting V/f frequency (6)

b110

0. to free-setting V/f frequency (7) (Hz)

Setting of the output

Free-setting V/f frequency (5)

b108

0. to free-setting V/f frequency (6) (Hz)

frequency at each

Free-setting V/f frequency (4)

b106

0. to free-setting V/f frequency (5) (Hz)

breakpoint of the V/f

Free-setting V/f frequency (3)

b104

0. to free-setting V/f frequency (4) (Hz)

characteristic curve

Free-setting V/f frequency (2)

b102

0. to free-setting V/f frequency (3) (Hz)

 

Free-setting V/f frequency (1)

b100

0. to free-setting V/f frequency (2) (Hz)

 

Free-setting V/f voltage (7)

b113

 

 

Free-setting V/f voltage (6)

b111

 

Setting of the output

Free-setting V/f voltage (5)

b109

 

0.0 to 800.0(V)

voltage at each

Free-setting V/f voltage (4)

b107

breakpoint of the V/f

Free-setting V/f voltage (3)

b105

 

 

characteristic curve (*1)

Free-setting V/f voltage (2)

b103

 

 

 

Free-setting V/f voltage (1)

b101

 

 

(Example)

Output voltage (V)

V7

V6

V5

V4

V1

V2,V3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Output frequency (Hz)

0

f1

f2

f3

f4

f5

f6

f7

 

*1 Even if 800 V is set as a free-setting V/f voltage (1 to 7), the inverter output voltage cannot exceed the inverter input voltage or that specified by the AVR voltage select.

Carefully note that selecting an inappropriate control system (V/f characteristic) may result in overcurrent during motor acceleration or deceleration or vibration of the motor or other machine driven by the inverter.

Output voltage (V)

V7

Voltage that can be output by the inverter or that was specified by the AVR voltage select

V6

0

f6

f7

Output frequency (Hz)

 

 

 

4 - 17