Related code
b001: Selection of restart mode
b002: Allowable under-voltage power failure time
b003: Retry wait time before motor restart
b004: Instantaneous power failure/under-voltage trip alarm enable
b005: Number of restarts on power failure/under-voltage trip events b007: Restart frequency threshold
b008: Selection of retry count after undervoltage
C021 to C025: Terminal [11] to [15] functions
C026: Alarm relay terminal function

Chapter 4 Explanation of Functions

4.2.27 Retry or trip after instantaneous power failure

(1) Retry (restart) after instantaneous power failure You can select tripping or retrying (restarting) the motor operation as the inverter operation to be performed at the occurrence of instantaneous power failure or undervoltage.

If you specify a retry operation for the selection of restart mode (b001), the inverter will retry the motor operation for the number of times set as "b005" after an instantaneous power failure or the number of times set as "b009" after overvoltage respectively, and then trip if all retries fail. (The inverter will not trip if you specify an unlimited number of retries.)

With function "b004" you can select whether to make the inverter trip when an instantaneous power failure or undervoltage occur while the inverter is in a stopped state.

When selecting a retry operation, also set the retry conditions listed below according to the system to be driven by the inverter.

Even during a retry operation, the inverter will trip with error code "E09" (undervoltage) displayed if the undervoltage status continues for 40 seconds.

Item

Function code

Data or range of

Description

data

 

 

 

 

 

00

Tripping

 

 

01

Restarting the motor with 0 Hz at retry

 

 

02

Starting the motor with a matching frequency at retry

Selection of restart mode

 

(See example 1.) (*3)

b001

 

 

Starting the motor with a matching frequency at retry

(*4) (*6)

 

 

03

The inverter trips after decelerating and stopping the

 

 

 

 

 

motor. (*1) (*3)

 

 

04

Restarting the motor with an input frequency at retry

 

 

(See example 1.) (*3)

 

 

 

 

 

 

Restarting the motor when the power failure duration does

Allowable under-voltage

b002

0.3 to 25.0 (s)

not exceed the specified time (See example 1.)

power failure time

Tripping when the power failure duration exceeds the

 

 

 

 

 

specified time (See example 2.)

Retry wait time before

b003

0.3 to 100. (s)

Time to wait until restarting the motor

motor restart

 

 

 

Instantaneous power

 

00

Disabling the inverter from tripping

 

01

Enabling the inverter to trip

failure/under-voltage trip

b004

 

Disabling the inverter from tripping when the inverter is

alarm enable (*2) (*4)

 

02

stopped or while the motor is being decelerated or

 

 

 

stopped after the operation command has been turned off

Number of restarts on

 

00

Retrying the motor operation up to 16 times after

 

instantaneous power failure

power failure/under-voltage

b005

 

 

Retrying the motor operation an unlimited number of times

trip events

 

01

 

after instantaneous power failure

 

 

 

 

 

 

Restarting the motor with 0 Hz if the frequency becomes

Restart frequency threshold

b007

0.00 to 400.0 (Hz)

less than the frequency set here during motor free-running

 

 

 

(See examples 3 and 4.)

 

 

00

Tripping

 

 

01

Restarting the motor with 0 Hz at retry

Trip/retry selection

b008

02

Starting the motor with a matching frequency at retry

 

Starting the motor with a matching frequency at retry

 

 

03

The inverter trips after decelerating and stopping the

 

 

 

motor.

 

 

04

Restarting the motor with an input frequency at retry

 

 

00

Retrying the motor operation up to 16 times after

Selection of retry count

b009

undervoltage

 

after undervoltage

01

Retrying the motor operation an unlimited number of times

 

 

 

after undervoltage

 

 

 

Selection of retry count

 

 

Number of retries to be made after the occurrence of

after overvoltage or

b010

1 to 3 (times)

overvoltage or overcurrent (*5)

overcurrent

 

 

 

 

 

Retry wait time after

b011

0.3 to 100. (s)

Time to wait until restarting the motor

overvoltage or overcurrent

 

 

 

Active frequency matching,

b030

00

Frequency set when the inverter output has been shut off

01

Maximum frequency

restart frequency select

 

02

Newly set frequency

 

 

Active frequency matching,

 

"0.20 x rated

 

b028

current" to "2.00 x

Current limit for restarting with active matching frequency

scan start frequency

 

rated current"

 

 

 

 

Active frequency matching,

b029

0.10 to 30.00 (s)

Duration of frequency lowering when restarting with active

scan-time constant

matching frequency

 

 

4 - 33