Chapter 4 Explanation of Functions

(vii)06 command: This command reads a specified setting item from the inverter. - Transmission frame

Frame format

STX

Station No. Command Parameter

BCC

CR

 

Description

Data size

Setting

STX

Control code (Start of TeXt)

1 byte

STX (0x02)

Station No.

Station number of control-target

2 bytes

01 to 32

inverter

 

 

 

Command

Command to be transmitted

2 bytes

06

Parameter

Data parameter number

4 bytes

See Note 12.

BCC

Block check code

2 bytes

XOR of the items from "Station No." to "Data."

See Item (3) of this section.

 

 

 

CR

Control code (Carriage Return)

1 byte

CR (0x0D)

Note 12: The parameters that can be specified for reading are F002 to F004, A001 to A153, b001 to b132, C001 to C159, H003 to H073, and P001 to P131. (To read the F001 parameter, use the 01 command.)

-Response frame Positive response: Frame format

STX

Station No.

ACK

Data

BCC

CR

 

 

 

Description

 

 

Data size

 

 

 

 

 

Setting

 

 

 

 

 

STX

 

Control code (Start of TeXt)

 

1 byte

 

STX (0x02)

 

 

 

 

 

 

 

 

Station No.

Station number of control-target

 

2 bytes

 

01 to 32

 

 

 

 

 

 

 

 

inverter

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ACK

 

Control code (acknowledgement)

 

1 byte

 

ACK (0x06)

 

 

 

 

 

 

 

 

Data

 

Data to be sent (decimal ASCII

 

8 bytes

 

See Note 13.

 

 

 

 

 

 

 

 

 

code)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BCC

 

Block check code

 

 

 

2 bytes

 

XOR of the items from "Station No." to "Data."

 

 

 

 

 

See Item (3) of this section.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CR

 

Control code (Carriage Return)

 

1 byte

 

CR (0x0D)

 

 

 

 

 

 

 

 

Note 13: When the read parameter is an selection item, the Data part contains the code data

 

 

 

 

corresponding to the selection.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The code data corresponding to "H003" or "H203" (motor capacity selection) is as follows:

 

 

Code data

 

00

01

 

02

 

03

04

05

 

06

07

 

08

 

09

 

10

Japan or U.S.A. mode

 

0.2 kW

-

 

0.4

 

-

0.75

-

 

1.5

2.2

 

-

 

3.7

 

-

(b085 = 00 or 02)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EU mode (b085 = 01)

 

0.2 kW

0.37

 

-

 

0.55

0.75

1.1

 

1.5

2.2

 

3.0

 

-

 

4.0

 

Code data

 

11

12

 

13

 

14

15

16

 

17

18

 

19

 

20

 

21

Japan or U.S.A. mode

 

5.5 kW

7.5

 

11

 

15

18.5

22

 

30

37

 

45

 

55

 

75

(b085 = 00 or 02)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EU mode (b085 = 01)

 

5.5 kW

7.5

 

11

 

15

18.5

22

 

30

37

 

45

 

55

 

75

For the value contained in the Data part when the read parameter is a numerical item, see the list of function codes.

(Example) When the setting of the acceleration (1) time (F002) is 30.00 seconds, the Data part contains "3000".

Negative response: See Item (2)-(ii) of this section.

4 - 123

Page 181
Image 181
Hitachi SJ700-2 instruction manual Response frame Positive response Frame format, Station No. Command Parameter, Byte ACK