Chapter 4 Explanation of Functions
4.2.77 Window comparators (WCO/WCOI/WCO2) (detection of terminal disconnection: ODc/OIDc/O2Dc)
Related code
C021 to C025: Terminal [11] to terminal [15] functions
- The window comparator function outputs C026: Alarm relay terminal function
b060/b063/b066: Maximum-limit level of window comparators O/OI/O2
signals when the values of analog inputs O, b061/b064/b067: Minimum-limit level of window comparators O/OI/O2
OI, and O2 are within the maximum and
minimum limits specified for the window comparator. You can monitor analog inputs with reference to arbitrary levels (to find input terminal disconnection and other errors).
- You can specify a hysteresis width for the maximum-limit and minimum-limit levels of the window comparator.
- You can specify limit levels and a hysteresis width individually for analog inputs O, OI, and O2.
- You can fix the analog input data to be applied to an arbitrary value when WCO, WCOI, or WCO2 is output. For this purpose, specify a desired value as the operation level at O/OI/O2 disconnection (b070/b071/b072). When "no" is specified, the analog input data is reflected as input.
- Output values of ODc, OIDc, and O2Dc are the same as those of WCO, WCOI, and WCO2, respectively.

Item

Function

 

Range of data

Description

code

 

 

 

 

 

 

 

 

27

ODc: Detection of analog input O

 

 

 

disconnection

Terminal [11] to terminal

 

 

 

 

 

28

OIDc: Detection of analog input OI

[15] functions

 

 

disconnection

C021-C025

 

 

 

 

 

O2Dc: Detection of analog input O2

 

C026

 

29

 

 

disconnection

 

 

 

 

Alarm relay terminal

 

 

54

WCO: Window comparator O

 

 

55

WCOI: Window comparator OI

function

 

 

 

 

56

WCO2: Window comparator O2

 

 

 

Maximum-limit level of

b060 (O )

 

"Minimum-limit level + hysteresis width/2

 

b063 (OI)

 

(minimum of 0)" to 100. (%)

 

window comparators

 

Setting of maximum-limit level

 

 

"Minimum-limit level + hysteresis width/2

O/OI/O2

b066 (O2)

 

 

 

(minimum of -100)" to 100. (%)

 

 

 

 

 

Minimum-limit level of

b061 (O )

 

0 to "maximum-limit level - hysteresis

 

b064 (OI)

 

width/2 (maximum of 100)" (%)

Setting of minimum-limit level

window comparators

 

 

 

-100 to "maximum-limit level - hysteresis

O/OI/O2

b067 (O2)

 

 

 

width/2 (maximum of 100)" (%)

 

 

 

 

 

Hysteresis width of

b062 (O )

 

0 to "(maximum-limit level - minimum-limit

Setting of hysteresis width for

window comparators

b065 (OI)

 

maximum-limit and minimum-limit

 

level)/2 (maximum of 10)" (%)

O/OI/O2

b068 (O2)

 

levels

 

 

Operation level at

b070 (O )

 

0 to 100 (%) or "no" (ignore)

Setting of the analog input value to be

b071 (OI)

 

applied when WCO, WCOI, or WCO2

O/OI/O2 disconnection

 

 

 

 

 

(ODc, OIDc, or O2Dc) is output.

b072 (O2)

 

-100 to 100 (%) or "no" (ignore)

 

 

 

 

 

O, OI, or O2

 

 

 

 

Max(100%)

Hysteresis width

 

 

 

 

 

 

(b062,b065,b068)

 

 

 

 

 

Maximum-limit level of window

 

 

 

 

comparator (b061/b064/b067)

 

 

 

Applied analog data

Analog operation level at

 

 

 

 

 

 

 

 

disconnection (b070/b071/b072)

 

 

 

 

Minimum-limit level of window

Min(O/OI:0%)

Applied analog data

comparator (b060/b063/b066)

 

(O2 :-100%)

 

 

 

 

WCO/WCOI/WCO2

ODc/OIDc/O2Dc

4 - 71