Hitachi SJ700-2 instruction manual Sensorless vector control, H021/H221/H031

Models: SJ700-2

1 274
Download 274 pages 15.86 Kb
Page 147
Image 147
Related code A001: Frequency source setting
A044/A244: V/F characteristic curve selection, 1st/2nd motors
F001: Output frequency setting
b040: Torque limit selection
b041 to b044: Torque limits (1) to (4)
H002/H202: Motor data selection, 1st/2nd motors
H003/H203: Motor capacity, 1st/2nd motors
H004/H204: Motor poles setting, 1st/2nd motors
H005/H205: Motor speed constant, 1st/2nd motors
H020/H220: Motor constant R1, 1st/2nd motors
H021/H221: Motor constant R2, 1st/2nd motors
H022/H222: Motor constant L, 1st/2nd motors
H023/H223: Motor constant Io, 1st/2nd motors
H024/H224: Motor constant J, 1st/2nd motors
H050/H250: PI proportional gain, 1st/2nd motors
H051/H251: PI integral gain, 1st/2nd motors
H052/H252: P proportional gain setting, 1st/2nd motors
Chapter 4 Explanation of Functions

4.2.96 Sensorless vector control

The sensorless vector control function estimates and controls the motor speed and output torque on the basis of the inverter output voltage and output current and the motor constants set on the inverter. This function enables the inverter to accurately operate the motor with a high starting torque, even at a low frequency (0.3 Hz or more).

To use this function, specify "03" for the V/F characteristic curve selection (A044/A244).

Before using this function, be sure to make optimum constant settings for the motor with reference to Section 4.2.91, "Motor constant selection."

When using this function, observe the following precautions:

1) If you use the inverter to drive a motor of which the capacity is two classes lower than the maximum applicable capacity of the inverter, you may not be able to obtain adequate motor characteristics.

2)If you cannot obtain the desired characteristics from the motor driven under the sensorless vector control, readjust the motor constants according to the symptom, as described in the table below.

Operation

Symptom

Adjustment method

Adjustment item

status

 

 

 

 

Momentary speed

Increase the motor constant R2 step by step from the

H021/H221/H031

Powering

variation is negative.

set value up to 1.2 times as high as the set value.

 

Momentary speed

Reduce the motor constant R2 step by step from the set

H021/H221/H031

 

 

variation is positive.

value down to 0.8 times as high as the set value.

 

 

Torque is insufficient at

Increase the motor constant R1 step by step from the

H020/H220/H030

Regenerating

low frequencies

set value up to 1.2 times as high as the set value.

 

Increase the motor constant Io step by step from the set

 

 

(several Hz)

H023/H223/H033

 

 

value up to 1.2 times as high as the set value.

 

Starting

The motor generates an

Reduce the motor constant J from the set value.

H024/H224/H034

 

impact when it starts.

 

 

Decelerating

The motor runs

Reduce the speed response setting.

H005/H205

unsteadily.

Reduce the motor constant J from the set value.

H024/H224/H034

 

 

Torque is insufficient

 

 

Torque-limited

during torque-limited

Reduce the overload restriction level to lower than the

b021, b041 to b044

operation

operation at a low

torque limiter level.

 

 

frequency.

 

 

Low-frequency

Motor rotation is

Increase the motor constant J from the set value.

H024/H224/H034

operation

inconsistent.

 

 

starting

Motor runs backwards

Set 01 (enable) on reverse run protection function

b046

for short moment.

(b046)

 

 

Note 1: Always set the carrier frequency (b083) to 2.1 kHz or more. If the carrier frequency is less than 2.1 kHz, the inverter cannot operate the motor normally.

Note 2: When driving a motor of which the capacity is one class lower than the inverter, adjust the torque limit (b041 to b044) so that the value "α" calculated by the expression below does not exceed 200%. Otherwise, the motor may be burnt out.

α= "torque limit" x (inverter capacity)/(motor capacity)

(Example) When the inverter capacity is 0.75 kW and the motor capacity is 0.4 kW, the torque limit value is calculated as follows, based on the assumption that the value "α" should be 200%:

Torque limit (b041 to b044) = α x (motor capacity)/(inverter capacity) = 200% x (0.4 kW)/(0.75 kW) = 106%

4 - 89

Page 147
Image 147
Hitachi SJ700-2 instruction manual Sensorless vector control, H021/H221/H031