Chapter 8 List of Data Settings

 

 

 

 

 

Default

Setting

Change

 

 

 

 

 

 

during

during

 

 

Code

Function name

Monitored data or setting

 

 

 

 

operation

operation

Page

 

 

 

 

_FF

 

_FEF

_FUF

(allowed

(allowed

 

 

 

 

 

 

or not)

or not)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C038

Low-current indication signal

00 (output during acceleration/deceleration and constant-speed operation),

 

01

 

¯

{

 

 

output mode selection

01 (output only during constant-speed operation)

 

 

4-69

 

 

 

 

 

 

 

 

 

C039

Low-current indication signal

0.0 to 2.00 x "rated current" (A)

Rated current of inverter

{

{

 

 

 

detection level

 

 

 

 

 

 

 

 

 

 

 

 

C040

Overload signal output mode

00 (output during acceleration/deceleration and constant-speed operation),

 

01

 

¯

{

 

 

01 (output only during constant-speed operation)

 

 

4-40

 

 

 

 

 

 

 

 

 

 

C041

Overload level setting

0.0 to 2.00 x "rated current" (A)

Rated current of inverter

{

{

 

 

C042

Frequency arrival setting for accel.

0.00 to 99.99, 100.0 to 400.0 (Hz)

 

0.00

 

¯

{

4-62

 

C043

Frequency arrival setting for decel.

0.00 to 99.99, 100.0 to 400.0 (Hz)

 

0.00

 

¯

{

 

 

 

 

status

C044

PID deviation level setting

0.0 to 100.0 (%)

 

3.0

 

¯

{

4-29

C045

Frequency arrival setting for

0.00 to 99.99, 100.0 to 400.0 (Hz)

 

0.00

 

¯

{

 

terminal

 

acceleration (2)

 

 

 

 

 

 

 

4-62

C046

Frequency arrival setting for

0.00 to 99.99, 100.0 to 400.0 (Hz)

 

0.00

 

¯

{

 

 

 

 

 

 

 

 

deceleration (2)

 

 

 

 

 

 

 

 

 

 

 

 

 

output

C052

Maximum PID feedback data

0.0 to 100.0 (%)

 

100.0

 

¯

{

4-29

C053

Minimum PID feedback data

0.0 to 100.0 (%)

 

0.0

 

¯

{

and

C055

Over-torque (forward-driving) level

0. to 200. (%)

 

100.

 

¯

{

 

Levels

setting

 

 

 

 

 

 

 

 

 

 

 

 

C056

Over-torque (reverse

0. to 200. (%)

 

100.

 

¯

{

 

 

 

regenerating) level setting

 

 

 

 

 

 

 

4-65

 

C057

Over-torque (reverse driving) level

0. to 200. (%)

 

100.

 

¯

{

 

 

 

 

 

setting

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C058

Over-torque (forward

0. to 200. (%)

 

100.

 

¯

{

 

 

regenerating) level setting

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C061

Electronic thermal warning level

0. to 100. (%)

 

80.

 

¯

{

4-38

 

setting

 

 

 

 

 

 

 

 

 

 

 

 

 

C062

Alarm code output

00 (disabling), 01 (3 bits), 02 (4 bits)

 

00

 

¯

{

4-65

 

C063

Zero speed detection level

0.00 to 99.99, 100.0 (Hz)

 

0.00

 

¯

{

4-64

 

C064

Heat sink overheat warning level

0. to 200.0 (°C)

 

120.

 

¯

{

4-68

 

C071

Communication speed selection

02 (loopback test), 03 (2,400 bps), 04 (4,800 bps), 05 (9,600 bps), 06

 

04

 

¯

{

 

 

(19,200 bps)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C072

Node allocation

1. to 32.

 

1.

 

¯

{

 

function

C074

Communication data length

00 (no parity), 01 (even parity), 02 (odd parity)

 

00

 

¯

{

 

Communication parity selection

 

 

 

 

C073

selection

7 (7 bits), 8 (8 bits)

 

7

 

¯

{

 

 

 

 

 

 

 

 

 

 

 

Communication

 

 

 

 

 

 

 

 

 

 

C075

Communication stop bit selection

1 (1 bit), 2 (2 bits)

 

1

 

¯

{

4-113

 

 

 

 

 

Selection of the operation after

00 (tripping), 01 (tripping after decelerating and stopping the motor), 02

 

 

 

 

 

 

 

 

C076

(ignoring errors), 03 (stopping the motor after free-running), 04

 

02

 

¯

{

 

 

communication error

 

 

 

 

 

(decelerating and stopping the motor)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C077

Communication timeout limit

0.00 to 99.99 (s)

 

0.00

 

¯

{

 

 

before tripping

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C078

Communication wait time

0. to 1000. (ms)

 

0.

 

¯

{

 

 

C079

Communication mode selection

00(ASCII), 01(Modbus-RTU)

 

00

 

¯

{

 

Adjustment

C081

[O] input span calibration

0. to 9999., 1000 to 6553(10000 to 65530)

Factory setting

{

{

 

C085

Thermistor input tuning

0.0 to 999.9, 1000.

Factory setting

{

{

4-72

 

C082

[OI] input span calibration

0. to 9999., 1000 to 6553(10000 to 65530)

Factory setting

{

{

 

C083

[O2] input span calibration

0. to 9999., 1000 to 6553(10000 to 65530)

Factory setting

{

{

 

 

 

 

 

 

 

 

 

 

 

 

C091

Debug mode enable

(Do not change this parameter, which is intended for factory adjustment.)

 

00

 

¯

¯

 

C101

Up/Down memory mode selection

00 (not storing the frequency data), 01 (storing the frequency data)

 

00

 

¯

{

4-56

Others

C102

Reset mode selection

00 (resetting the trip when RS is on), 01 (resetting the trip when RS is off), 2

 

00

 

{

{

4-54

(enabling resetting only upon tripping [resetting when RS is on])

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C103

Restart mode after reset

00 (starting with 0 Hz), 01 (starting with matching frequency), 02 (restarting

 

00

 

¯

{

 

 

with active matching frequency)

 

 

 

 

 

 

 

 

 

 

 

 

 

Meter adjustment

C105

FM gain adjustment

50. to 200. (%)

 

100.

 

{

{

4-73

C109

AM bias adjustment

0. to 100. (%)

 

0.

 

{

{

 

 

C106

AM gain adjustment

50. to 200. (%)

 

100.

 

{

{

 

 

C107

AMI gain adjustment

50. to 200. (%)

 

100.

 

{

{

4-74

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C110

AMI bias adjustment

0. to 100. (%)

 

20.

 

{

{

 

8 - 11