Hitachi SJ700-2 instruction manual Low-current indication LOC signal, Forward rotation signal FWR

Models: SJ700-2

1 274
Download 274 pages 15.86 Kb
Page 127
Image 127
Chapter 4 Explanation of Functions
Related code
C021 to C025: Terminal [11] to [15] functions
C026: Alarm relay terminal function
C038: Low-current indication signal output mode selection
C039: Low-current indication signal detection level

4.2.72 Low-current indication (LOC) signal

The inverter outputs the low-current indication (LOC) signal when the inverter output current falls to the low-current indication signal detection level (C039) or less.

You can select one of the two signal output modes with the low-current indication signal output mode selection (C038). In one mode, the LOC signal output is always enabled during the inverter operation. In the other mode, the LOC signal output is enabled only while the inverter is driving the motor for constant-speed operation.

Item

Function code

Data or range of data

Description

Terminal function

C021 to C025

43

LOC: Low-current indication signal

Alarm relay terminal function

C026

 

 

Low-current indication signal

 

00

Enabling the signal output during

C038

operation

 

output mode selection

01

Enabling the signal output only

 

 

 

during constant-speed operation (*1

 

 

 

Low-current indication signal

C039

0.0 to "2.0 x rated

Setting of the threshold current level

at which to output the low-current

detection level

current" (A)

 

indication signal

 

 

 

(*1) When 01 (control circuit terminal) is selected as frequency source setting (A001), there is a case that inverter does not recognize the speed as constant value due to sampling. In this case, adjusting is to be made by setting C038=00 (valid during operation) or increasing analogue input filter (A016).

Output current (A)

Low-current indication signal detection level (C039)

Low-currentON indication signal

ON

4.2.73 Inverter ready signal (IRDY)

Related code

The inverter outputs the inverter ready (IRDY) signal when it is ready for C021 to C025: Terminal [11] to [15] functions

operation (i.e., when it can receive an operation command).

C026: Alarm relay terminal function

-The inverter can recognize only the operation command that is input while the IRDY signal is output.

-If the IRDY signal is not output, check whether the input power supply voltage (connected to the R, S, and T terminals) is within the range of specification.

-Signal is not output when the power is given only to control power supply.

Item

Function code

Data or range of data

Description

Terminal function

C021 to C025

50

IRDY: Inverter ready signal

Alarm relay terminal function

C026

 

 

4.2.74 Forward rotation signal (FWR)

The inverter continues to output the forward rotation (FWR) signal while it is driving the motor for forward operation.

The FWR signal is turned off while the inverter is driving the motor for reverse operation or stopping the motor.

Related code

C021 to C025: Terminal [11] to [15] functions

C026: Alarm relay terminal function

Item

Function code

 

Data or range of data

Description

Terminal function

C021 to C025

 

51

FWR: Forward rotation signal

Alarm relay terminal function

C026

 

 

 

 

 

 

4 - 69

 

Page 127
Image 127