Chapter 4 Explanation of Functions

The commands are described below.

(i)00 command: This command instructs the inverter to drive the motor (for forward or reverse rotation) or stop the motor. (To use this command, set "A002" to "03" [RS485].)

-Transmission frame Frame format

STX

Station No.

Command

Data

BCC

CR

 

Description

Data size

Setting

STX

Control code (Start of TeXt)

1 byte

STX (0x02)

Station No.

Station number of control-target

2 bytes

01 to 32, or FF (broadcast to all stations)

inverter

 

 

 

Command

Command to be transmitted

2 bytes

00

Data

Data to be transmitted

1 byte

See Note 1.

BCC

Block check code

2 bytes

XOR of the items from "Station No." to "Data."

See Item (3) of this section.

 

 

 

CR

Control code (Carriage Return)

1 byte

CR (0x0D)

Note 1:

 

 

 

Data

Description

 

Remarks

0

Stop command

 

 

1

Forward rotation command

 

 

2

Reverse rotation command

 

 

(Example) When sending a forward rotation command to the inverter with station No. 01:

(STX) 01001 (BCC) (CR) Conversion into ASCII format 0230 3130 303133 300D - Response frame

Positive response: See Item (2)-(i) of this section.

Negative response: See Item (2)-(ii) of this section.

(ii)01 command: This command sets the inverter output frequency. (To use this command, set "A001" to "03" [RS485].)

-Transmission frame Frame format

STX

Station No.

Command

Data

BCC

CR

 

Description

Data size

Setting

STX

Control code (Start of TeXt)

1 byte

STX (0x02)

Station No.

Station number of control-target

2 bytes

01 to 32, or FF (broadcast to all stations)

inverter

 

 

 

Command

Command to be transmitted

2 bytes

01

Data

Data to be sent (decimal ASCII

6 bytes

See Note 2.

code)

 

 

 

BCC

Block check code

2 bytes

XOR of the items from "Station No." to "Data."

See Item (3) of this section.

 

 

 

CR

Control code (Carriage Return)

1 byte

CR (0x0D)

Note 2: For example, to set the output frequency of the inverter with station No. 01 to 5 Hz, the data is as follows:

(STX) 0101000500 (BCC) (CR) 0230 3130 3130 30 30 35 30 3030 350D

Note 3: The data indicates a value 100 times as large as the actual frequency value to be set.

(Example) 5 (Hz) 500 000500 30 30 30 35 30 30

Note 4: When using the data as the feedback data for PID control, set the most-significant byte to "1".

(Example) 5 (%) 500 100500 31 30 30 35 30 30

- Response frame

Positive response: See Item (2)-(i) of this section.

Negative response: See Item (2)-(ii) of this section.

4 - 117