Chapter 4 Explanation of Functions

(iii)02, 12 command: This command turns the specified intelligent input terminals on or off. - Transmission frame

Frame format

STX

Station No.

Command

Data

BCC

CR

 

Description

Data size

Setting

STX

Control code (Start of TeXt)

1 byte

STX (0x02)

Station No.

Station number of control-target

2 bytes

01 to 32, or FF (broadcast to all stations)

inverter

 

 

 

Command

Command to be transmitted

2 bytes

02

Data

Data to be transmitted

16 bytes

See Note 5.

BCC

Block check code

2 bytes

XOR of the items from "Station No." to "Data."

See Item (3) of this section.

 

 

 

CR

Control code (Carriage Return)

1 byte

CR (0x0D)

Note 5: The table below lists the functions of the intelligent input terminals and corresponding hexadecimal data. (For details, see the explanation of the intelligent input terminal functions.)

Data

Description

Data

Description

(hexadecimal)

(hexadecimal)

 

 

0000000000000001

FW: Forward rotation

0000000100000000

SF1: Multispeed bit 1

0000000000000002

RV: Reverse rotation

0000000200000000

SF2: Multispeed bit 2

0000000000000004

CF1: Multispeed 1 setting

0000000400000000

SF3: Multispeed bit 3

0000000000000008

CF2: Multispeed 2 setting

0000000800000000

SF4: Multispeed bit 4

0000000000000010

CF3: Multispeed 3 setting

0000001000000000

SF5: Multispeed bit 5

0000000000000020

CF4: Multispeed 4 setting

0000002000000000

SF6: Multispeed bit 6

0000000000000040

JG: Jogging

0000004000000000

SF7: Multispeed bit 7

0000000000000080

DB: External DC braking

0000008000000000

OLR: Overload restriction selection

0000000000000100

SET: Set 2nd motor data

0000010000000000

TL: Enabling /disabling torque limitation

0000000000000200

2CH: 2-stage acceleration/deceleration

0000020000000000

TRQ1: Torque limit selection bit 1

0000000000000400

-

0000040000000000

TRQ2: Torque limit selection bit 2

0000000000000800

FRS: Free-run stop

0000080000000000

PPI: P/PI mode selection

0000000000001000

EXT: External trip

0000100000000000

BOK: Braking confirmation

0000000000002000

USP: Unattended start protection

0000200000000000

ORT: Orientation

0000000000004000

CS: Commercial power source enable

0000400000000000

LAC: LAD cancellation

0000000000008000

SFT: Software lock

0000800000000000

PCLR: Clearance of position deviation

0000000000010000

AT: Analog input voltage/current select

0001000000000000

STAT: Pulse train position command input enable

0000000000020000

SET3: 3rd motor control

0002000000000000

-

0000000000040000

RS: Reset

0004000000000000

ADD: Trigger for frequency addition

0000000000080000

-

0008000000000000

F-TM: Forcible-terminal operation

0000000000100000

STA: Starting by 3-wire input

0010000000000000

ATR: Permission of torque command input

0000000000200000

STP: Stopping by 3-wire input

0020000000000000

KHC: Cumulative power clearance

0000000000400000

F/R: Forward/reverse switching by 3-wire input

0040000000000000

SON: Servo On

0000000000800000

PID: Enabling/disabling PID

0080000000000000

FOC: Forcing

0000000001000000

PIDC: PID reset

0100000000000000

MI1: General-purpose input 1

0000000002000000

-

0200000000000000

MI2: General-purpose input 2

0000000004000000

CAS: Control gain setting

0400000000000000

MI3: General-purpose input 3

0000000008000000

UP: Remote control UP function

0800000000000000

MI4: General-purpose input 4

0000000010000000

DWN: Remote control DOWN function

1000000000000000

MI5: General-purpose input 5

0000000020000000

DWN: Remote control data clearing

2000000000000000

MI6: General-purpose input 6

0000000040000000

-

4000000000000000

MI7: General-purpose input 7

0000000080000000

OPE: Forcible operation

8000000000000000

MI8: General-purpose input 8

4 - 118

Page 176
Image 176
Hitachi SJ700-2 instruction manual Data to be transmitted