Chapter 4 Explanation of Functions

(3)Restarting methods

-Restart with matching frequency

The inverter detects the frequency and rotation direction based on the residual voltage in the motor, and then restarts the motor based on the detected frequency.

-Restart with input frequency

The inverter starts the output with the frequency specified for the start frequency selection (b030), searches for the point where the frequency and voltage are balanced while keeping the current at the restart current level (b028), and then restarts the motor.

If the inverter trips when it restarts the motor in this way, reduce the setting of "b028".

-After the inverter output has been shut off, the digital operator continues to display until the inverter restarts the motor operation.

FW

FRS

b028

Output current

Deceleration according to the setting of "b029"

Inverter output

 

frequency

Frequency selected as the

 

 

setting of "b030"

Motor speed

b003

4.2.28 Phase loss power input protection

Related code

The phase loss power input protection function gives a warning when phase loss power is input to the inverter.

b006: Phase loss detection enable

Item

Function code

Data

Description

Phase loss detection

b006

00

Disabling the protection

enable

01

Enabling the protection

 

An phase loss power input may cause the following conditions, resulting in an inverter failure:

(1)The ripple current increases in the main capacitor, and the capacitor life will be shortened significantly.

(2)When the inverter is connected to a load, the internal converter or thyristor of the inverter may be damaged.

4 - 36

Page 94
Image 94
Hitachi SJ700-2 instruction manual Phase loss power input protection, Function code Data Description Phase loss detection