Related code A145: Frequency to be added
A146: Sign of the frequency to be added
C001 to C008: Terminal [1] to [8]functions

Chapter 4 Explanation of Functions

4.2.13 Frequency addition function

The frequency addition function allows you to add or subtract the value specified as the frequency to be added (A145) to or from the frequency value of a selected frequency command.

To use this function, assign function "50" (ADD) to an intelligent input terminal.

When the ADD terminal is turned on, the inverter performs the addition or subtraction of the value specified as "A145".

Item

Function code

Data or range of data

Description

Frequency to be added

A145

0.00 to 400.00(Hz)

Setting of the frequency to be added

Selection of the sign of the

A146

00

(Frequency command) + (A145)

frequency to be added

01

(Frequency command) - (A145)

 

Terminal function

C001 to C008

50

ADD selection of the trigger for adding

the frequency (A145)

 

 

 

Note 1: If the sign of the frequency value in the frequency command changes from minus (-) to plus (+), or vice versa, as the result of frequency addition, the motor operation direction will be inverted.

Note 2: When the PID function is used, the frequency addition function can apply to PID target data. (In such cases, the data display by function "A145" is in percentage [in steps of 0.01%]).

4.2.14 Start/end frequency setting for external analog input

The start/end frequency setting function

 

 

Related code

 

allows you to set the inverter output

 

 

 

 

[OI]-[L] input active range start current

 

 

 

A011: [O]-[L] input active range start frequency

A103:

 

 

 

A012: [O]-[L] input active range end frequency

A104: [OI]-[L] input active range end current

frequency in relation to the external analog A013: [O]-[L] input active range start voltage

A105: [OI]-[L] input start frequency enable

inputs (frequency commands) via the

A014: [O]-[L] input active range end voltage

A111: [O2]-[L] input active range start frequency

A015: [O]-[L] input start frequency enable

A112: [O2]-[L] input active range end frequency

following terminals:

 

A101: [OI]-[L] input active range start frequency

A113: [O2]-[L] input active range start voltage

O-L terminal: 0 to 10 V

 

A102: [OI]-[L] input active range end frequency

A114: [O2]-[L] input active range end voltage

 

 

 

 

 

 

OI-L terminal: 4 to 20 mA

 

 

 

 

 

 

O2-L terminal: -10 to +10 V

 

 

 

 

 

(1) Start/end frequency settings for the O-L and OI-L terminals

 

 

 

 

 

 

 

 

 

 

Item

 

Function code

Range of data

 

 

Description

[O]/[OI]-[L] input active

 

A011/A101

0.00 to

Setting of the start frequency

range start frequency

 

400.0(Hz)

 

 

 

 

 

 

 

 

 

 

[O]/[OI]-[L] input active

 

A012/A102

0.00 to

Setting of the end frequency

range end frequency

 

400.0(Hz)

 

 

 

 

 

 

 

 

 

 

[O]/[OI]-[L] input active

 

A013/A103

0. to 100.(%)

Setting of the rate of the start frequency to the

range start voltage

 

external frequency command (0 to 10 V/0 to 20 mA)

 

 

 

[O]/[OI]-[L] input active

 

A014/A104

0. to 100.(%)

Setting of the rate of the end frequency to the

range end voltage

 

external frequency command (0 to 10 V/0 to 20 mA)

 

 

 

 

 

 

 

Externally input start frequency

 

 

 

00

The frequency set as "A011" or "A101" is output as

 

 

 

the output frequency while the start-frequency rate is

[O]/[OI]-[L] input start

 

 

 

 

A015/A105

 

0% to the value set as "A013" or "A103".

frequency enable

 

 

0 Hz

 

 

 

 

 

 

 

 

 

 

01

0 Hz is output as the output frequency while the

 

 

 

start-frequency rate is 0% to the value set as "A013"

 

 

 

 

 

 

 

 

or "A103".

 

 

If the voltage of the signal to be input to the O-L terminal is 0 to 5 V, specify 50% for "A014".

(Example 1) A015/A105: 00

 

(Example 2) A015/A105: 01

Maximum frequency

A012/A102

Out put frequency in the range from 0% to A013/A103 is A011/A101

Maximum frequency

A012/A102

Out put frequency in the range from 0% to A013/A103 is 0Hz

A011/A101

 

 

 

 

 

Analog input

A011/A101

 

 

 

 

 

 

Analog input

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0 A013/A103 A014/A104 100%

0 A013/A103

A014/A104 100%

(0 V/0 mA)

 

(10 V/20 mA)

(O/OI)

(0 V/0 mA)

 

(10 V/20 mA)

(O/OI)

4 - 14

Page 72
Image 72