Chapter 4 Explanation of Functions

4.4.2 Communication in Modbus-RTU mode

(1) Communication protocol

The communication between the inverter (slave) and external control system (master) is based on the following protocol:

(1)

(1)

External control system

Inverter

(2)

Time

Waiting time (silent interval + communication wait time [C078])

(3) Communication trip limit time (C077)

(If reception timeout occurs, the inverter will operate according to the setting of the operation selection after communication error [C076].)

(1): Query frame that is sent from the external control system to the inverter

(2): Response frame that is sent from the inverter to the external control system

(3): Communication trip limit time (C077)

If the inverter cannot complete the reception of a query from the master system (external control system) within the communication trip limit time, after having sent a response to the preceding query, the inverter enters the status in which to receive the query from the beginning. Subsequently, the inverter returns no response to the master system.

After reception timeout occurs, the inverter operates according to the setting of the selection of operation after communication error (C076). For details, see the table below. Monitoring of reception timeout begins when the first communication is performed after the inverter power has been turned on or the inverter has been reset. Reception timeout is monitored only when the inverter communicates with the master system.

Item

Function code

Range of data

Description

 

 

00: Tripping

The inverter trips (E41) after reception

 

 

timeout.

 

 

 

 

 

01: Tripping after

The inverter decelerates and stops the

 

 

motor, and then trips (E41) after reception

 

 

stopping the motor

 

 

timeout.

 

 

 

Selection of operation

C076

02: Ignoring the errors

The inverter ignores the error without tripping

and alarm output.

after communication error

 

 

03: Stopping the

The inverter stops the motor after

 

 

 

 

motor after

free-running without tripping and alarm

 

 

free-running (FRS)

output after reception timeout.

 

 

04: Decelerating and

The inverter decelerates and stops the motor

 

 

without tripping and alarm output after

 

 

stopping the motor

 

 

reception timeout.

 

 

 

Communication trip limit

C077

0.00 to 99.99 (s)

Limit time to determine the reception timeout

time setting

 

 

 

 

 

 

Time to wait until the inverter starts sending a

Communication wait time

C078

0. to 1000. (ms)

response after reception of a query

 

 

 

(excluding the silent interval)

The inverter sends a response (frame (2)) always after receiving a query (frame (1)). The inverter does not actively output any frame to the external control system.

4 - 129

Page 187
Image 187
Hitachi SJ700-2 instruction manual Communication in Modbus-RTU mode