Sample connection diagram and timing charts for
commercial power supply switching MC2
Related code
b003: Retry wait time before motor restart
b007: Restart frequency threshold
C001 to C008: Terminal [1] to [8] functions

Chapter 4 Explanation of Functions

(Example 3) Restarting with active matching frequency

After the retry wait time (b003), the

 

 

 

 

inverter restarts the motor with the

FW

 

frequency set as "b030". The inverter

 

 

subsequently decelerates the motor

 

 

according to the setting of "b029"

FRS

 

while maintaining the output current

 

b028

at the level specified for "b029".

Output current

 

When the output voltage matches

 

the frequency, the inverter

 

Deceleration according to

re-accelerates the motor up to the

 

the setting of "b029"

frequency that was set when the

Inverter output

 

inverter shut off the output to the

 

motor before the restart.

frequency

Frequency selected as the

If the inverter trips because of

 

overcurrent when it restarts the

 

setting of "b030"

 

motor with input frequency, reduce

 

 

Motor speed

 

the setting of "b028".

b003

4.2.48 Commercial power source switching (CS) function

The commercial power source switching function allows you to switch the power supply (between the inverter and commercial power supply) to your system of which the load causes a considerable moment of inertia. You can use the inverter to accelerate and decelerate the motor in the system and the commercial power supply to drive the motor for constant-speed operation.

To use this function, assign function "14" (CS) to one of the terminal [1] to [8] functions (C001 to C008). When the CS terminal is turned off with an operation command being input, the inverter waits for the retry wait time before motor restart (b003), adjusts the output frequency to the speed of the free-running motor, and then accelerates the motor with the adjusted frequency. (The start mode is the starting with matching frequency.) However, the inverter may start the motor with 0 Hz if:

1)the motor speed is no more than half the base frequency or

2)the voltage induced on the motor is attenuated quickly.

3)If the motor speed falls to the restart frequency threshold (b007), the inverter will start the motor with 0 Hz. (See Section 4.2.27.)

Remark) Mechanically interlock the MC3 and MC2 contacts with each other. Otherwise you may damage the drive.

If the earth-leakage breaker (ELB) trips because of a ground fault, the commercial power will be disabled. Therefore, connect a backup power supply from the commercial power line circuit (ELBC) to your system if

needed.

Use weak-current type relays for FWY, RVY, and CSY. The figures below show the sequence and timing of operations for reference.

If the inverter trips because of overcurrent

NFB

ELBC

 

MC1

 

MC3

THRY

 

 

 

when it starts the motor with matching

 

 

 

R

U

 

Motor

frequency, increase the retry wait time

 

 

 

S

V

 

before motor restart (b003).

 

 

 

T

W

 

 

 

 

 

R0

 

 

 

For circuit connections and switching

 

 

 

 

 

 

 

 

 

T0

 

 

 

operations, see the sample connection

 

 

 

 

 

 

 

 

 

H

 

 

 

diagram and timing charts for commercial

 

 

 

 

 

 

 

 

 

O

 

 

 

power supply switching as shown on the

 

 

 

 

 

 

 

 

 

L

AL1

 

 

right.

 

 

 

 

 

 

 

 

 

 

AL2

 

 

The inverter can be set up so that it will

 

 

 

FW

 

 

 

 

 

AL0

 

 

automatically retry operation at power-on.

 

 

FWY

RV

 

 

 

 

 

 

 

In such cases, the CS terminal (signal)

 

 

RVY

CS

 

 

 

shown in the figures below is not required.

 

 

CSY

CM1

 

 

 

For details, see the explanation of the

 

 

 

 

 

 

 

reset (RS) function (4.2.29).

 

 

 

 

 

 

 

4 - 53

Page 111
Image 111
Hitachi SJ700-2 instruction manual Commercial power source switching CS function