Hitachi SJ700-2 200 to 240 V +10%, -15%, 50/60 Hz ±5% 282 to 339 VDC, 380 to 480 V +10%, -15%

Models: SJ700-2

1 274
Download 274 pages 15.86 Kb
Page 39
Image 39

Chapter 2 Installation and Wiring

(4)Recommended cable gauges, wiring accessories, and crimp terminals

Note: For compliance with CE and UL standards, see the safety precautions concerning EMC and the compliance with UL and CUL standards under Safety Instructions.

The table below lists the specifications of cables, crimp terminals, and terminal screw tightening torques for reference.

200 V class

400 V class

 

 

Gauge of power

 

External braking

 

 

 

Applicable device

Motor

 

line cable (mm2)

 

Size of

 

Tightening

 

Grounding

 

 

 

output

Applicable inverter

(Terminals: R, S,

resistor across

terminal

Crimp

torque

 

 

 

Magnetic

model

cable (mm2)

terminals P and

terminal

Earth-leakage

(kW)

 

T, U, V, W, P, PD,

 

RB (mm2)

screw

 

(N-m)

breaker (ELB)

contactor

 

 

and N)

 

 

 

 

 

 

(MC)

5.5

SJ700-055LFF2

5.5

5.5

5.5

M5

R5.5-5

2.4

EX50B (50A)

HK25

 

 

 

 

 

 

 

 

 

 

7.5

SJ700-075LFF2

8

8

8

M5

R8-5

2.4

EX60 (60A)

HK35

 

 

 

 

 

 

 

 

 

 

11

SJ700-110LFF2

14

14

14

M6

R14-6

4.5

RX100 (75A)

HK50

 

 

 

 

 

 

 

 

 

 

15

SJ700-150LFF2

22

22

22

M6

22-6

4.5

RX100 (100A)

H65

 

 

 

 

 

 

 

 

 

 

18.5

SJ700-185LFF2

30

22

30

M6

30-S6

4.5

RX100 (100A)

H80

38-8

 

 

 

 

 

 

 

 

 

22

SJ700-220LFF2

38

30

38

M8

38-S8

8.1

RX225B (150A)

H100

38-10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

60-S8

 

 

 

30

SJ700-300LFF2

60 (22×2)

30

M8

60-10

8.1

RX225B (200A)

H125

CB60-8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CB60-S8

 

 

 

37

SJ700-370LFF2

100 (38×2)

38

M8

100-8

8.1

RX225B (225A)

H150

 

 

 

 

 

 

 

 

 

 

45

SJ300-450LFF2

100 (38×2)

38

M8

100-8

8.1

RX225B (225A)

H200

 

 

 

 

 

 

 

 

 

 

55

SJ300-550LFF2

150 (60×2)

60

M10

150-10

8.1

RX400B (350A)

H250

5.5

SJ700-055HFF2

2

2

2

M5

R2-5

2.4

EX50C (30A)

HK20

 

 

 

 

 

 

 

 

 

 

7.5

SJ700-075HFF2

3.5

3.5

3.5

M5

3.5-5

2.4

EX50C (30A)

HK25

 

 

 

 

 

 

 

 

 

 

11

SJ700-110HFF2

5.5

5.5

5.5

M6

R5.5-6

4.5

EX50C (30A)

HK35

 

 

 

 

 

 

 

 

 

 

15

SJ700-150HFF2

8

8

8

M6

8-6

4.5

EX60B (60A)

HK35

 

 

 

 

 

 

 

 

 

 

18.5

SJ700-185HFF2

14

14

14

M6

14-6

4.5

EX60B (60A)

HK50

 

 

 

 

 

 

 

 

 

 

22

SJ700-220HFF2

14

14

14

M6

14-6

4.5

RX100 (75A)

HK50

30

SJ700-300HFF2

22

22

M6

22-6

4.5

RX100 (100A)

H65

 

 

 

 

 

 

 

 

 

 

37

SJ700-370HFF2

38

22

M8

38-8

8.1

RX100 (100A)

H80

 

 

 

 

 

 

 

 

 

 

45

SJ700-450HFF2

38

22

M8

38-8

8.1

RX225B (150A)

H100

 

 

 

 

 

 

 

 

 

 

55

SJ700-550HFF2

60

30

M8

R60-8

8.1

RX255B (175A)

H125

 

 

 

 

 

 

 

 

 

 

Note: Cable gauges indicate those of HIV cables (maximum heat resistance: 75°C).

(5)Connecting the control circuit to a power supply separately from the main circuit

If the protective circuit of the inverter operates to open the magnetic contactor in the input power supply circuit, the inverter control circuit power is lost, and the alarm signal cannot be retained.

To retain the alarm signal, connect control circuit terminals R0 and T0 to a power supply.

In details, connect the control circuit power supply terminals R0 and T0 to the primary side of the

magnetic contactor as shown below.

 

 

(Connection method)

 

 

Power-receiving specifications

 

 

200 V class model:

 

Remove the connected cables.

200 to 240 V (+10%, -15%)

 

Remove the J51 connector.

(50/60 Hz ±5%)

 

 

 

(282 to 339 VDC)

 

Connect the control circuit power

400 V class model:

 

supply cables to the control

380 to 480 V (+10%, -15%)

 

circuit power supply terminal

(50/60 Hz ±5%)

J51

block.

 

(537 to 678 VDC)

 

 

Note the following when connecting separate power supplies to control circuit power supply terminals

(R0 and T0) and main circuit power supply terminals (R, S, and T):

-Use a cable thicker than 1.25 mm2 to connect the terminals R0 and T0 (terminal screw size: M4).

-Connect a 3 A fuse in the control circuit power supply line.

-If the control circuit power supply (connected to R0 and T0) is turned on earlier than the main circuit power supply (connected to R, S, and T), ground fault is not checked at power-on.

-When supplying DC power to the control circuit power supply terminals (R0 and T0), specify "00" as the "a/b (NO/NC)" selection (function code C031 to C036) for intelligent output terminals ([11] to [15]) and intelligent relay terminals (AL0, AL1, and AL2). If "01" is specified as the "a/b (NO/NC)" selection, output signals may chatter when the DC power supply is shut off.