Chapter 4 Explanation of Functions

(iv)03 command: This command reads all monitored data from the inverter. - Transmission frame

Frame format

STX

Station No.

Command

BCC

CR

 

Description

Data size

Setting

STX

Control code (Start of TeXt)

1 byte

STX (0x02)

Station No.

Station number of control-target

2 bytes

01 to 32

inverter

 

 

 

Command

Command to be transmitted

2 bytes

03

BCC

Block check code

2 bytes

XOR of the items from "Station No." to "Data."

See Item (3) of this section.

 

 

 

CR

Control code (Carriage Return)

1 byte

CR (0x0D)

-Response frame Frame format

STX

Station No.

Data

BCC

CR

 

Description

Data size

Setting

STX

Control code (Start of TeXt)

1 byte

STX (0x02)

Station No.

Station number of control-target

2 bytes

01 to 32

inverter

 

 

 

Data

Data

104 bytes

See Note 7.

BCC

Block check code

2 bytes

XOR of the items from "Station No." to "Data."

See Item (3) of this section.

 

 

 

CR

Control code (Carriage Return)

1 byte

CR (0x0D)

Note 7: Monitored data

Monitoring item

Unit

Magnifica-

Data size

Description

 

tion

 

 

 

 

 

 

 

 

Output frequency

Hz

×100

 

8 bytes

Decimal ASCII code

 

 

 

High-

Output current

A

×10

 

8 bytes

Decimal ASCII code

 

Rotation direction

-

-

 

8 bytes

"0" stopping, "1" (forward rotation), or "2"

 

 

 

 

 

 

(reverse rotation)

 

order

 

 

 

 

 

 

 

PID feedback data

%

×100

 

8 bytes

Decimal ASCII code

 

bytes

Intelligent input terminal

-

-

 

8 bytes

See Note 7.

 

 

 

 

Intelligent output terminal

-

-

 

8 bytes

See Note 8.

 

Low-

Frequency conversion

-

×100

 

8 bytes

Decimal ASCII code

 

Output torque

%

×1

 

8 bytes

Decimal ASCII code

 

 

 

order

Output voltage

V

×10

 

8 bytes

Decimal ASCII code

 

 

 

 

Electric power

kW

×10

 

8 bytes

Decimal ASCII code

 

bytes

-

-

-

 

8 bytes

Always "00000000" (reserved for data storage)

 

 

 

 

Cumulative running time

h

×1

 

8 bytes

Decimal ASCII code

 

Cumulative power-on time

h

×1

 

8 bytes

Decimal ASCII code

 

 

 

 

Note 8: Monitoring of intelligent input terminals

Note 8: Monitoring of intelligent output terminals

 

Terminal

Data

FW terminal

00000001

Terminal 1

00000002

Terminal 2

00000004

Terminal 3

00000008

Terminal 4

00000010

Terminal 5

00000020

Terminal 6

00000040

Terminal 7

00000080

Terminal 8

00000100

Terminal

Data

Relay terminal

00000001

Terminal 11

00000002

Terminal 12

00000004

Terminal 13

00000008

Terminal 14

00000010

Terminal 15

00000020

4 - 120