Chapter 5 Error Codes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Name

Description

Display on

 

Display on

Troubleshooting and corrective action

Reference

 

digital operator

remote operator

page

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check for the noise sources located near the

 

 

Gate array

If an error occurs in the communication

 

 

 

 

 

 

 

 

inverter.

 

 

 

 

 

 

 

 

 

 

(Remove noise sources.)

-

 

communica-

between the internal CPU and gate

 

 

 

 

 

 

GA.COM

 

 

 

 

 

 

 

 

 

Check whether the communication cable has

 

tion error

array, the inverter will trip.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

been disconnected.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Check the connectors.)

 

 

 

When the phase loss input protection

 

 

 

 

 

 

 

 

Check for the phase loss power input.

 

 

Phase loss

has been enabled (b006 = 01), the

 

 

 

 

 

 

 

 

(Check the power supply input wiring.)

 

 

inverter will trip to avoid damage if an

 

 

 

 

 

 

 

 

Check the MCB and magnetic contactors for

 

 

input

 

 

 

 

 

 

PH.fail

 

-

 

phase loss input is detected. The inverter

 

 

 

 

 

 

 

poor contacts.

 

protection

trips when the phase loss input

 

 

 

 

 

 

 

 

(Replace the MCB and magnetic contactors.)

 

 

 

continues for about 1 second or more.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check for the noise sources located near the

 

 

 

The inverter will trip if the gate array

 

 

 

 

 

 

 

 

inverter.

 

 

Main circuit

 

 

 

 

 

 

 

 

(Remove noise sources.)

 

 

cannot confirm the on/off state of IGBT

 

 

 

 

 

 

 

 

Check the main circuit element for damage.

-

 

 

 

 

 

 

 

Main.Cir

 

 

error (*3)

because of a malfunction due to noise or

 

 

 

 

 

 

 

Check the output circuit for a short circuit.

 

 

 

 

 

 

 

 

 

 

 

 

damage to the main circuit element.

 

 

 

 

 

 

 

 

(Check the IGBT.)

 

 

 

 

 

 

 

 

 

 

 

 

Check the inverter for abnormality.

 

 

 

 

 

 

 

 

 

 

 

 

(Repair the inverter.)

 

 

 

If instantaneous overcurrent occurs, the

 

 

 

 

 

 

 

 

Check the output circuit for a short circuit.

 

 

 

main circuit element temperature is

 

 

 

 

 

 

 

 

(Check the output cables.)

 

 

 

abnormal, or the main circuit element

 

 

 

 

 

 

 

 

Check for the ground fault.

 

 

IGBT error

drive power drops, the inverter will shut

 

 

 

 

 

 

 

 

(Check the output cables and motor.)

-

 

off its output to protect the main circuit

 

 

 

 

 

 

IGBT

 

Check the main circuit element for damage.

 

 

element. (After tripping because of this

 

 

 

 

 

 

 

 

(Check the IGBT.)

 

 

 

protective function, the inverter cannot

 

 

 

 

 

 

 

 

Check the heat sink for clogging.

 

 

 

retry the operation.)

 

 

 

 

 

 

 

 

(Clean the heat sink.)

 

 

 

The inverter monitors the resistance of

 

 

 

 

 

 

 

 

Check whether the motor temperature is high.

 

 

 

the thermistor (in the motor) connected

 

 

 

 

 

 

 

 

(Check the motor temperature.)

 

 

 

to the inverter's TH terminal, and will

 

 

 

 

 

 

 

 

Check whether the internal thermistor of the

 

 

Thermistor

shut off the inverter output if the motor

 

 

 

 

 

 

 

 

motor has been damaged.

2-8

 

temperature rises.

 

 

 

 

 

 

TH

 

(Check the thermistor.)

 

error

 

 

 

 

 

 

 

4-70

 

 

 

 

 

 

 

 

 

 

Check whether noise has been mixed in the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

thermistor signal.

 

 

 

 

 

 

 

 

 

 

 

 

(Separate the thermistor wiring from other

 

 

 

 

 

 

 

 

 

 

 

 

wirings.)

 

 

 

When "01" has been specified for the

 

 

 

 

 

 

 

 

Check whether the brake has been turned on

 

 

 

Brake Control Enable (b120), the

 

 

 

 

 

 

 

 

and off or not.

 

 

 

inverter will trip if it cannot receive the

 

 

 

 

 

 

 

 

(Check the brake.)

 

 

Braking error

braking confirmation signal within the

 

 

 

 

 

 

 

 

Check whether the wait time (b124) is too

4-79

 

Brake Wait Time for Confirmation (b124)

 

 

 

 

 

 

BRAKE

 

short.

 

 

after the output of the brake release

 

 

 

 

 

 

 

 

(Increase the wait time [b124].)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

signal.

 

 

 

 

 

 

 

 

Check whether the braking confirmation

 

 

 

 

 

 

 

 

 

 

 

 

signal has been input.

 

 

 

 

 

 

 

 

 

 

 

 

(Check the wiring.)

 

 

 

If the EMR signal (on three terminals) is

 

 

 

 

 

 

 

 

Check whether an error has occurred in the

 

 

Emergency

turned on when the slide switch (SW1)

 

 

 

 

 

 

 

 

external equipment since the emergency stop

 

 

on the logic board is set to ON, the

 

 

 

 

 

 

 

 

function was enabled.

2-8

 

 

 

 

 

 

 

EMR

 

 

stop (*4)

inverter hardware will shut off the

 

 

 

 

 

 

 

(Recover the external equipment from the

 

 

 

 

 

 

 

 

 

 

 

 

inverter output and display the error code

 

 

 

 

 

 

 

 

error.)

 

 

 

shown on the right.

 

 

 

 

 

 

 

 

 

 

 

 

If overload occurs during the motor

 

 

 

 

 

 

 

 

 

 

 

 

operation at a very low speed at 0.2 Hz

 

 

 

 

 

 

 

 

 

 

 

Low-speed

or less, the electronic thermal protection

 

 

 

 

 

 

 

 

Check whether the motor load is too high.

 

 

overload

circuit in the inverter will detect the

 

 

 

 

 

 

OL-LowSP

 

-

 

overload and shut off the inverter output.

 

 

 

 

 

(Reduce the load factor.)

 

protection

 

 

 

 

 

 

 

 

 

 

(2nd electronic thermal control)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Note that a high frequency may be

 

 

 

 

 

 

 

 

 

 

 

 

recorded as the error history data.)

 

 

 

 

 

 

 

 

 

 

 

 

If timeout occurs because of line

 

 

 

 

 

 

 

 

Check whether the communication speed

 

 

Modbus

disconnection during the communication

 

 

 

 

 

 

 

 

setting is correct.

 

 

in Modbus-RTU mode, the inverter will

 

 

 

 

 

 

 

 

Check whether the wiring distance is

4-106

 

communica-

display the error code shown on the

 

 

 

 

 

 

NET.ERR

 

appropriate.

 

tion error

right. (The inverter will trip according to

 

 

 

 

 

 

 

 

(Check the connections.)

 

 

 

the setting of "C076".)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check whether the option board is mounted

Refer to the

 

 

The inverter detects errors in the option

 

 

 

 

 

 

OP1-0

 

correctly.

instruction

 

 

 

 

 

 

 

 

 

(Check the board mounting.)

 

 

 

 

 

 

 

 

Option 1 error

board mounted in the optional slot 1. For

 

to

 

 

 

manual for

 

details, refer to the instruction manual for

 

 

 

 

Check whether the option board is used

the SJ-FB,

 

 

the mounted option board.

 

 

 

 

 

 

 

 

correctly.

SJ-DG, or

 

 

 

 

 

 

 

 

OP1-9

 

(Check the instruction manual for the option

 

 

 

 

 

 

 

 

 

 

 

board.)

SJ-DN.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*3 The inverter will not accept reset commands input via the RS terminal or entered by the STOP/RESET key. Therefore, turn off the inverter power.

*4 The inverter will not accept the reset command entered from the digital operator. Therefore, reset the inverter by turning on the RS terminal.

5 - 3

Page 225
Image 225
Hitachi SJ700-2 instruction manual Ga.Com