Hitachi SJ700-2 instruction manual DC braking DB setting

Models: SJ700-2

1 274
Download 274 pages 15.86 Kb
Page 78
Image 78

Chapter 4 Explanation of Functions

4.2.19 DC braking (DB) setting

The DC braking function allows you to apply DC braking to the motor according to the load on the motor.

You can control DC braking in two ways: the external control through signal input to intelligent input terminals and the internal control to be performed automatically when the motor is started and stopped.

Note that the motor cannot be stopped by DC braking if the load on the motor produces a large moment of inertia.

Related code

A051: DC braking enable

A052: DC braking frequency setting

A053: DC braking wait time

A054: DC braking force during deceleration

A055: DC braking time for deceleration

A056: DC braking/edge or level detection for [DB] input

A057: DC braking force for starting

A058: DC braking time for starting

A059: DC braking carrier frequency setting

C001 to C008: Terminal [1] to [8] functions

Item

Function code

Data or range of data

Description

 

 

00

Internal DC braking is disabled.

DC braking enable

A051

01

Internal DC braking is enabled.

02

Internal DC braking is enabled. (The braking

 

 

 

 

operates only with the set braking frequency.)

 

 

 

DC braking

 

 

With internal DC braking enabled, DC braking is

A052

0.00 to 60.00 (Hz)

started when the output frequency reaches the

frequency setting

 

 

set braking frequency.

 

 

 

DC braking wait

 

 

The DC braking wait time specifies the delay in

A053

0.0 to 5.0 (s)

starting DC braking after the set braking time has

time

 

 

elapsed or the DB terminal has been turned on.

 

 

 

DC braking force

 

 

 

during deceleration/

A054/A057

0. to 100. (%)

"0" specifies the smallest force (zero current);

DC braking force for

"100" specifies the largest force (rated current).

 

 

starting

 

 

 

DC braking time for

A055

0.0 to 60.0 (s)

This setting is valid for the external DC braking in

deceleration

edge mode or for the internal DC braking.

 

 

DC braking/edge or

A056

00

Edge mode (See examples 1-a to 6-a.)

level detection for

01

Level mode (See examples 1-b to 6-b.)

[DB] input

 

 

 

 

DC braking time for

 

 

This setting is valid for the internal DC braking.

A058

0.0 to 60.0 (s)

DC braking is started when the motor-start

starting

 

 

command is input.

 

 

 

DC braking carrier

A059

0.5 to 15 (kHz)

Unit: kHz

frequency setting

 

 

 

(1) Carrier frequency for DC braking

Use the DC braking carrier frequency setting (A059) to specify the carrier frequency for DC braking. Note that setting the carrier frequency above 5 kHz automatically lowers the braking force.

See the following graph showing the operation of the DC braking force limiter:

100

90

80

(75)

 

70

 

Maximum braking

60

 

50

(46)

force (%)

40

(34)

 

 

30

(22)

 

 

20

 

 

 

 

 

(10)

10

 

 

 

 

 

 

 

 

 

 

 

3

5

7

9

11

13

15

DC braking carrier frequency (kHz)

DC braking force limiter

4 - 20

Page 78
Image 78
Hitachi SJ700-2 instruction manual DC braking DB setting