Chapter 4 Explanation of Functions

4.2.11 External analog input setting (O, OI, and O2)

The inverter has the following three types of external analog input terminals:

O-L terminal: 0 to 10 V

OI-L terminal: 4 to 20 mA

O2-L terminal: -10 to 10 V

Related code

A005: [AT] selection

A006: [O2] selection

C001 to C008: Terminal [1] to [8] functions

The table below lists the settings of the external analog input terminals.

Item

Function

Data

 

Description

code

 

 

 

 

 

 

 

00

Switching between the O and OI

Turning on the AT terminal enables the OI-L terminal.

 

 

terminals with the AT terminal

Turning on the AT terminal enables the O-L terminal.

 

 

 

 

 

01

Switching between the O and O2

Turning on the AT terminal enables the O2-L terminal.

 

 

terminals with the AT terminal

Turning on the AT terminal enables the O-L terminal.

 

 

 

 

 

(02)

(Valid only when the OPE-SR is used)

Turning on the AT terminal enables the pot on

[AT]

A005

Switching between the O terminal and

OPE-SR terminal.

 

the control with the AT terminal

Turning on the AT terminal enables the O-L terminal.

selection

 

 

(03)

(Valid only when the OPE-SR is used)

Turning on the AT terminal enables the pot on

 

 

 

 

Switching between the OI terminal and

OPE-SR terminal.

 

 

 

the control with the AT terminal

Turning on the AT terminal enables the OI-L terminal.

 

 

(04)

(Valid only when the OPE-SR is used)

Turning on the AT terminal enables the pot on

 

 

Switching between the O2 terminal

OPE-SR terminal.

 

 

 

and the control with the AT terminal

Turning on the AT terminal enables the O2-L terminal.

 

 

00

Using the O2 terminal independently

 

 

 

01

Using the O2 terminal for auxiliary frequency command (nonreversible) in addition to the O and

[O2]

A006

OI terminals

 

 

 

selection

02

Using the O2 terminal for auxiliary frequency command (reversible) in addition to the O and OI

 

 

 

terminals

 

 

 

 

 

 

 

03

Disabling the O2 terminal

 

Note that whether frequency commands are input to the O2-L terminal and whether the motor operation is reversible depend on the combination of settings of functions "A005" and "A006" and whether function "16" (AT) is assigned to an intelligent input terminal as shown in the table below.

When the motor operation is reversible, the inverter operates the motor in a reverse direction if the sum of the frequencies specified by the main frequency and auxiliary frequency commands is less than 0 (even when the forward operation [FW] terminal is on). Even when no wire is connected to the 02 terminal, reverse operation of the motor may occur and prolong the acceleration time if the output voltage fluctuates near 0 V.

 

 

 

AT

 

Whether to input an auxiliary

Reversible/

 

A006

A005

Main frequency command

frequency command

 

terminal

nonreversible

 

 

 

 

(via the O2-L terminal)

 

 

 

 

 

 

 

 

00

OFF

O-L terminal

No input

Nonreversible

 

00,03

ON

OI-L terminal

No input

 

 

 

01

OFF

O-L terminal

No input

 

 

 

 

When the AT

 

ON

O2-L terminal

No input

Reversible

 

 

 

00

OFF

O-L terminal

Input

 

function is

 

 

 

(Example 1)

ON

OI-L terminal

Input

Nonreversible

assigned to an

01

 

OFF

O-L terminal

Input

 

intelligent input

 

01

 

 

ON

O2-L terminal

No input

Reversible

terminal

 

 

 

00

OFF

O-L terminal

Input

 

 

 

 

 

02

(Example 2)

ON

OI-L terminal

Input

Reversible

 

01

OFF

O-L terminal

Input

 

 

 

 

 

ON

O2-L terminal

No input

 

 

 

 

 

When the AT

00

O2-L terminal

No input

Reversible

01

Addition of signals on O-L and

Input

Nonreversible

function is not

OI-L terminals

 

 

 

 

 

assigned to any

02

Addition of signals on O-L and

Input

Reversible

intelligent input

OI-L terminals

 

 

 

 

 

terminal

 

 

 

 

 

 

03

Addition of signals on O-L and

No input

Nonreversible

 

OI-L terminals

 

 

 

 

 

 

4 - 12