Hitachi SJ700-2 instruction manual Offline auto-tuning function

Models: SJ700-2

1 274
Download 274 pages 15.86 Kb
Page 143
Image 143
Related code
H001: Auto-tuning Setting
H002: Motor data selection, 1st motor
H003: Motor capacity, 1st motor
H004: Motor poles setting, 1st motor
H030: Auto constant R1, 1st motor
H031: Auto constant R2, 1st motor
H032: Auto constant L, 1st motor
H033: Auto constant Io, 1st motor
H034: Auto constant J, 1st motor
A003: Base frequency setting
A051: DC braking selection
A082: AVR voltage select
b046: Reverse run proctection enable
Chapter 4 Explanation of Functions

4.2.92 Offline auto-tuning function

The offline auto-tuning function allows you to make the inverter automatically measure and set the motor constants that are required for the sensorless vector control, 0Hz-range sensorless vector control, and vector control with sensor.

When using the inverter to perform the sensorless vector control, 0Hz-range sensorless vector control, and vector control with sensor for a motor of which the motor constants are unknown, measure the motor constants with the offline tuning function.

When "00" (Hitachi general-purpose motor data) is specified for the motor constant selection (H002/H202), the motor constants of

Hitachi's general-purpose motors are set as defaults. When you drive a Hitachi's general-purpose motor with the inverter, you can usually obtain the desired motor characteristics without problems. (If you cannot obtain the desired characteristics, adjust the motor constant settings as described in Section 4.2.92 or 4.2.93.)

If you intend to use the online tuning function described later, be sure to perform offline auto-tuning beforehand.

The offline auto-tuning function applies only to the 1st motor and 2nd motor controls. Do not apply this function to the 3rd motor control.

The motor constant data corresponding to the date of one phase of γ connection at 50 Hz.

Item

Function code

Data or range of data

Description

 

 

00

Disabling the auto-tuning

Auto-tuning Setting

H001

01

Enabling the auto-tuning (without

motor rotation)

 

 

 

02

Enabling the auto-tuning (with motor

 

 

rotation)

 

 

 

 

 

00

Hitachi general-purpose motor data

Motor data selection

H002/H202

01

Automatically tuned data

02

Automatically tuned data (online

 

 

 

 

auto-tuning enabled)

 

 

 

Motor capacity

H003/H203

0.2 to 75.0 (kW)

 

Motor poles setting

H004/H204

2, 4, 6, 8, or 10 (poles)

 

Auto constant R1

H030/H230

0.000 to 65.53 (Ω)

 

Auto constant R2

H031/H231

0.000 to 65.53 kgm2

 

Auto constant L

H032/H232

0.00 to 655.3 (mH)

 

Auto constant Io

H033/H233

0.00 to 655.3 (A)

 

Auto constant J

H034H234

0.001 to 9999. (kgm2)

 

Base frequency

A003

30 to maximum frequency setting

 

setting

(Hz)

 

 

 

DC braking enable

A051

00

Disabling DC braking

01

Enabling DC braking

 

 

 

 

200, 215, 220, 230, or 240

Selectable only for 200 V class

AVR voltage select

A082

models

 

380, 400, 415, 440, 460, or 480

Selectable only for 400 V class

 

 

 

 

models

 

 

 

When using this function, follow the instructions below.

1)Adjust the settings of base frequency (A003) and AVR voltage select (A082) to the motor specifications. When motor voltage is other than the altanatives, set as ”motor voltage (A082) “ * ”outputr voltage gain (A045) “ = “motor rated voltage”

2)This function can properly apply to only the motors in the maximum applicable capacity class of your inverter or one class lower than the capacity class of your inverter. If this function is used for motors with other capacities, correct constant data may not be obtained. (In such cases, the auto-tuning operation may not be completed. If the auto-tuning operation is not completed, press the STOP/RESET key. The operation will end with an error code displayed.)

3)If "01" (enabling) is specified for the DC braking enable (A051), motor constants cannot be measured by offline auto-tuning. Specify "00" (disabling) for the DC braking enable. (The default setting is "00".)

4)If "02" (auto-tuning with motor rotation) is specified for the Auto-tuning Setting (H001), confirm or observe the following:

a)No problem occurs when the motor rotates at a speed close to 80% of the base frequency.

b)The motor is not driven by any other external power source.

4 - 85

Page 143
Image 143
Hitachi SJ700-2 instruction manual Offline auto-tuning function, When using this function, follow the instructions below