Hitachi SJ700-2 instruction manual Error code is output when the relevant program runs

Models: SJ700-2

1 274
Download 274 pages 15.86 Kb
Page 230
Image 230

Chapter 5 Error Codes

4) Error indications by protective functions with the easy sequence function used

 

 

Display on

Display on

Name

Description

remote operator

digital operator

 

 

 

ERR1***

 

 

 

 

 

 

-The inverter will display the error code shown on the right if an invalid instruction is found in a downloaded

Invalid instruction

program. (*1)

PRG.CMD

- The inverter will display the error code if the PRG

 

 

 

terminal is turned on when no program has been

 

 

loaded.

 

Nesting count

The inverter will display the error code shown on the

PRG.NST

right if subroutines, "for" instructions, and "next"

error

instructions are nested in more than eight levels.

 

 

 

-The inverter will display the error code shown on the right if the "for" or another instruction to start nesting is not found at the jump destination of a "go to" instruction, and the "next" or another instruction to end nesting precedes the nesting-start instruction.

-An error is assumed when an arithmetic operation

Execution error 1

instruction has resulted in overflow or underflow or a

PRG.ERR1

division by zero has been attempted.

 

 

-An error is assumed when a "chg param" or "mon param" instruction has attempted to reference an undefined parameter, set the data beyond the specified setting range in a parameter, or update a parameter that cannot be changed during the inverter operation.

PRG-0

User trips 0 to 9

The inverter outputs an error code when a trip instruction

is executed.

 

 

PRG-9

*1 The error code is output when the relevant program runs.