Hitachi SJ700-2 instruction manual Output of inverted PID deviation, 01 %

Models: SJ700-2

1 274
Download 274 pages 15.86 Kb
Page 86
Image 86

Chapter 4 Explanation of Functions

When you specify the 02 RS485 communication for the PV source setting (A076), transfer data as described below.

1) When the ASCII mode is selected (C078 = 00)

Use the 01 command for data transfer. To transfer feedback data, set the most-significant byte of frequency data to "1".

Example: When transmitting the frequency data specifying 5 Hz

The data to be transmitted consists of six bytes, indicating a value 100 times as large as the set frequency value. "000500"

Change the most-significant byte to "1". "100500" Convert the data to ASCII format. "31 30 30 35 30 30"

Note: In ASCII mode, the unit of setting is always frequency (Hz).

2) When the Modbus RTU mode is selected (C078 = 01)

Write the setting data (on the assumption that "10000" indicates 100%) to register address 0006h.

Register

Function name

Function code

Readable/writable

Monitored data or setting

Data

No.

 

 

(R/W)

 

resolution

0006h

PID feedback

R/W

0 to 10000

0.01 [%]

Note: This register is readable and writable. However, this register can be read only when Modbus RTU has been specified as the communication mode for PID feedback. It cannot be read with other settings.

- When pulse train input is specified for PID feedback, the input pulse train frequency (Hz) is converted to a percentage (with maximum frequency corresponding to 100%) and fetched as the feedback.

For the pulse train input frequency, see Section 4.3.21.

(4) Feed forward selection

-Select the terminal to be used for the feed forward signal through PID feed forward selection (A079).

-Even if the terminal selected for the target or feedback data is also selected for the terminal by A079, the terminal functions according to the setting of A079.

-Specifying the value to disable selection for A079 disables feed forward control.

(5) Output of inverted PID deviation

Some sensor characteristics may cause the polarity of the deviation of feedback data from the target value to be inconsistent with the inverter operation command. If the inconsistency occurs, specify "01" for function "A077" to invert the polarity of the deviation.

Example: When controlling the compressor for a refrigerator

Assume that the temperature and voltage specifications of the temperature sensor are -20°C to +100°C and 0 to 10 V and the target value is 0°C.

If the current temperature is 10°C and the inverter is under the normal type of PID control, the inverter will reduces the output frequency because the feedback data is larger than the target value.

In such a case, specify "01" for function "A077" to invert the feedback deviation. Then, the inverter will increase the output frequency.

A077

PID target value

-1

PID feedback data

PID

operation

(6) Limitation on PID variation range

You can limit the PID output to within a specific range with reference to the target value. To use the PID variation limit function, set the PID variation range (A078).

(Set a value on the assumption that the maximum frequency corresponds to 100%.) The variation of PID output is limited within ±"value of A078" from the target value. (Setting "0.0" for the PID variation range [A078] disables the PID variation limit function.) This function is deactivated when 0.0 is set on A078.

PID output (%)

 

PID output range

PID target value

 

PID variation range (A078)

 

(7) Output of inverted PID deviation

 

PID variation range (A078)

Time (s)

Page 86
Image 86
Hitachi SJ700-2 instruction manual Output of inverted PID deviation, 01 %