Chapter 4 Explanation of Functions

Register

Function name

Function

R/W

Monitoring and setting items Data resolution

Register

No.

code

No.

 

 

 

1326h

Reduced voltage start selection

b036

R/W

0 (minimum reduced voltage start time) to 255

-

 

 

 

 

(maximum reduced voltage start time)

 

1327h

Function code display restriction

b037

R/W

0 (full display), 1 (function-specific display), 2 (user

-

 

 

 

 

setting), 3 (data comparison display), 4 (basicdisplay)

 

1328h

Initial-screen selection

b038

R/W

0 (screen displayed when the STR key was pressed

-

 

 

 

 

last), 1 (d001), 2 (d002), 3 (d003), 4 (d007), 5 (F001)

 

1329h

Automatic user-parameter

b039

R/W

0 (disabling), 1 (enabling)

-

setting function enable

 

 

 

 

 

132Ah

Torque limit selection

b040

R/W

00 (quadrant-specific setting), 01 (switching by

-

terminal), 02 (analog input), 03 (option 1),

 

 

 

 

04 (option 2)

 

132Bh

Torque limit (1) (forward-driving

b041

R/W

0 to 200/255 (no)

1 [%]

in 4-quadrant mode)

 

 

 

 

 

132Ch

Torque limit (2)

b042

R/W

0 to 200/255 (no)

1 [%]

(reverse-regenerating in

 

4-quadrant mode)

 

 

 

 

132Dh

Torque limit (3) (reverse-driving

b043

R/W

0 to 200/255 (no)

1 [%]

in 4-quadrant mode)

 

 

 

 

 

 

Torque limit (4)

 

 

 

 

132Eh

(forward-regenerating in

b044

R/W

0 to 200/255 (no)

1 [%]

 

4-quadrant mode)

 

 

 

 

132Fh

Torque limit LADSTOP enable

b045

R/W

0 (disabling), 1 (enabling)

-

1330h

Reverse Run protection enable

b046

R/W

0 (disabling), 1 (enabling)

-

1331h to

(Reserved)

-

-

Inaccessible

-

1333h

 

 

 

 

 

 

Controller deceleration and stop

 

 

0 (disabling), 1 (enabling), 2, (nonstop operation at

 

1334h

b050

R/W

momentary power failure (no restoration))

-

 

on power loss

 

 

3, (nonstop operation at momentary power failure

 

 

 

 

 

(restoration to be done))

 

1335h

DC bus voltage trigger level

b051

R/W

0 to 10000

0.1 [V]

during power loss

 

 

 

 

 

1336h

Over-voltage threshold during

b052

R/W

0 to 10000

0.1 [V]

power loss

 

 

 

 

 

1337h

Deceleration time setting during

b053 (high)

R/W

0 to 360000

0.01

1338h

power loss (target voltage level)

b053 (low)

R/W

 

[sec.]

1339h

Initial output frequency decrease

b054

R/W

0 to 1000

0.01 [Hz]

during power loss

 

 

 

 

 

133Ah

Proportional gain setting for

b055

R/W

0 to 255

0.01

nonstop operation at momentary

 

power failure

 

 

 

 

 

Integral time setting for nonstop

 

 

 

0.001

133Bh

operation at momentary power

b056

R/W

0 to 65535

[sec]

 

failure

 

 

 

 

 

 

 

 

133Ch to

(Reserved)

-

-

Inaccessible

-

133Eh

 

 

 

 

 

133Fh

Maximum-limit level of window

b060

R/W

 

 

comparators O

 

 

 

 

 

 

 

1340h

Minimum-limit level of window

b061

R/W

 

 

comparators O

 

 

 

 

 

 

 

1341h

Hysteresis width of window

b062

R/W

 

 

comparators O

 

 

 

 

 

 

 

1342h

Maximum-limit level of window

b063

R/W

 

 

comparators OI

 

 

 

 

 

 

 

1343h

Minimum-limit level of window

b064

R/W

 

 

comparators OI

 

 

 

 

 

 

 

1344h

Hysteresis width of window

b065

R/W

 

 

comparators OI

 

 

 

 

 

 

 

1345h

Maximum-limit level of window

b066

R/W

 

 

comparators OI

 

 

 

 

 

 

 

1346h

Minimum-limit level of window

b067

R/W

 

 

comparators O/OI/O2

 

 

 

 

 

 

 

1347h

Hysteresis width of window

b068

R/W

 

 

comparators O/OI/O2

 

 

 

 

 

 

 

1348h

(Reserved)

-

-

Inaccessible

-

1349h

Operation level at O

b070

R/W

 

 

disconnection

 

 

 

 

 

 

 

134Ah

Operation level at OI

b071

R/W

 

 

disconnection

 

 

 

 

 

 

 

134Bh

Operation level at O2

b072

R/W

 

 

disconnection

 

 

 

 

 

 

 

134Ch to

(reserved)

-

-

Inaccessible

 

1350

 

 

 

 

 

1351h

Cumulative input power data

b060

R/W

Clearance by setting "1"

-

clearance

 

 

 

 

 

1352h

Cumulative input power display

b060

R/W

1 to 1000

1

gain setting

 

 

 

 

 

4 - 150

Page 208
Image 208
Hitachi SJ700-2 instruction manual Monitoring and setting items Data resolution Register