Hitachi SJ700-2 List of inverter trip factors, Option 1 error 0 to, Option 2 error 0 to

Models: SJ700-2

1 274
Download 274 pages 15.86 Kb
Page 201
Image 201

Chapter 4 Explanation of Functions

List of inverter trip factors

Upper part of trip factor code (indicating the factor)

Lower part of trip factor code (indicating the inverter

status)

 

 

 

 

Name

Code

Name

Code

No trip factor

0

Resetting

0

Overcurrent protection during

1

Stopping

1

constant-speed operation

 

 

 

Overcurrent protection during deceleration

2

Decelerating

2

Overcurrent protection during acceleration

3

Constant-speed operation

3

Overcurrent protection during stopping

4

Accelerating

4

Overload protection

5

Operating at zero frequency

5

Braking resistor overload protection

6

Starting

6

Overvoltage protection

7

DC braking

7

EEPROM error

8

Overload restricted

8

Undervoltage protection

9

SON or FOC operation in progress

9

CT error

10

 

 

CPU error

11

 

 

External trip

12

 

 

USP error

13

 

 

Ground-fault protection

14

 

 

Input overvoltage protection

15

 

 

Instantaneous power failure protection

16

 

 

Power-module temperature error (with the

20

 

 

fan stopped)

 

 

 

 

 

Power-module temperature error

21

 

 

Gate array communication error

23

 

 

Phase loss input protection

24

 

 

Main circuit error

25

 

 

IGBT error

30

 

 

Thermistor error

35

 

 

Braking error (added)

36

 

 

Emergency stop error

37

 

 

Electronic thermal protection at low speeds

38

 

 

Easy sequence error (invalid instruction)

43

 

 

Easy sequence error (invalid nesting count)

44

 

 

Easy sequence execution error 1

45

 

 

Easy sequence user trip 0 to 9

50 to 59

 

 

Option 1 error 0 to 9

60 to 69

 

 

Option 2 error 0 to 9

70 to 79

 

 

4 - 143