Hitachi SJ700-2 instruction manual Logical output signal operation function LOG1 to LOG6

Models: SJ700-2

1 274
Download 274 pages 15.86 Kb
Page 124
Image 124

Chapter 4 Explanation of Functions

Intelligent output terminals

 

 

When "4 bits" is selected

 

When "3 bits" is selected

14

13

 

12

11

Factor code

 

Cause of tripping

Factor code

Cause of tripping

AC3

AC2

 

AC1

AC0

 

 

 

 

 

 

 

 

 

 

 

1

1

 

0

1

 

E20, E21

Temperature error due to

 

 

 

 

 

low cooling-fan speed

 

 

 

 

 

 

 

 

 

Temperature error

 

 

 

1

1

 

1

0

 

E24

 

Phase loss input protection

 

1

1

 

1

1

E50 to E79

Easy sequence user trip 0-9,

 

 

option 1,2 error 0-9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Item

 

 

Function code

 

Data

 

 

Description

Alarm code output

 

 

 

C062

 

00

 

No output of alarm code

 

 

 

 

01

 

Output of 3-bit code

 

 

 

 

 

 

 

 

 

 

02

 

Output of 4-bit code

4.2.66 Logical output signal operation function (LOG1 to LOG6)

The logical output signal operation function allows you to make the inverter internally perform a logical operation of output signals.

This function applies to all output signals, except to logical operation results (LOG1 to LOG6).

Three types of operators (AND, OR, and XOR) are selectable.

Output signal 1

Output signal 2

LOGx (AND)

LOGx (OR)

LOGx (XOR)

Related code

C021 to C025: Terminal [11] to [15] functions

C026: Alarm relay terminal function

C142: Logical output signal 1 selection 1

C143: Logical output signal 1 selection 2

C144: Logical output signal 1 operator selection

C145: Logical output signal 2 selection 1

C146: Logical output signal 2 selection 2

C147: Logical output signal 2 operator selection

C148: Logical output signal 3 selection 1

C149: Logical output signal 3 selection 2

C150: Logical output signal 3 operator selection

C151: Logical output signal 4 selection 1

C152: Logical output signal 4 selection 2

C153: Logical output signal 4 operator selection

C154: Logical output signal 5 selection 1

C155: Logical output signal 5 selection 2

C156: Logical output signal 5 operator selection

C157: Logical output signal 6 selection 1

C158: Logical output signal 6 selection 2

C159: Logical output signal 6 operator selection

The necessary parameters depend on the logical output signal to be operated. The following table lists the parameters to be set for each logical output signal:

Selected signal

Operation-target 1

Operation-target 2

Operator

selection

selection

selection

 

33: Logical output signal 1 (LOG1)

C142

C143

C144

34: Logical output signal 2 (LOG2)

C145

C146

C147

35: Logical output signal 3 (LOG3)

C148

C149

C150

36: Logical output signal 4 (LOG4)

C151

C152

C153

37: Logical output signal 5 (LOG5)

C154

C155

C156

38: Logical output signal 6 (LOG6)

C157

C158

C159

(Example) To output the AND of the running signal (00: RUN) and set the frequency overreached signal (02: FA2) as the logical output signal 1 (LOG1) to the intelligent output terminal [2]:

-Intelligent output terminal [2] (C002): 33 (LOG1)

-Logical output signal 1 selection 1 (C142): 00 (RUN)

-Logical output signal 1 selection 2 (C143): 02 (FA2)

-Logical output signal 1 operator (C143): 00 (AND)

4 - 66