Chapter 4 Explanation of Functions

4.1.27 Trip monitoring 1 to 6

When the trip monitoring function (d081 to d086) is selected, the inverter displays the trip history data. The last six protective trips the inverter made can be displayed.

Select the trip monitoring 1 (d081) to display the data on the most recent trip.

Related code

d081: Trip monitoring 1

d082: Trip monitoring 2

d083: Trip monitoring 3

d084: Trip monitoring 4

d085: Trip monitoring 5

d086: Trip monitoring 6

(Display contents)

1)Factor of tripping (one of E01 to E79) (*1)

2)Output frequency at tripping (Hz)

3)Output current at tripping (A) (*2)

4)Main circuit DC voltage at tripping (V) (*3)

5)Cumulative inverter-running time until tripping (h)

6)Cumulative inverter power-on time until tripping (h) *1 See Section 5.1.1, "Protective functions."

*2 When the inverter status is in stop mode as a trip history, monitored value can be zero. *3 When grounding fault is detected at power on, monitored value can be zero.

(Display by trip monitoring)

1) Factor of

2) Frequency

3) Current at

4) Main circuit DC

5) Cumulative

6) Cumulative

tripping

at tripping

tripping

voltage at tripping

running time

power-on time

(*2)

 

 

 

 

 

 

 

 

 

 

 

 

 

FUNC

FUNC

*2 If the inverter has not tripped before, the inverter displays .

4.1.28 Programming error monitoring

If an attempt is made to set the data conflicting with other data on the inverter, the inverter displays a warning.

The PRG (program) lamp lights up while the warning is displayed (until the data is rewritten forcibly or corrected). For details on the programming error monitoring function, see Section 5.2. Warning Codes

4.1.29 DC voltage monitoring

When the DC voltage monitoring is selected, the inverter displays the DC voltage (across terminals P and N) of the inverter.

While the inverter is operating, the monitored value changes as the actual DC voltage of the inverter changes.

(Display)

0.0 to 999.9 in steps of 0.1 V

4.1.30 BRD load factor monitoring

When the BRD load factor monitoring function (d103) is selected, the inverter displays the BRD load factor. If the BRD load factor exceeds the value set as the dynamic braking usage ratio (b090), the inverter will trip because of the braking resistor overload protection (error code "E06").

(Display)

0.0 to 100.0 in steps of 0.1%

4.1.31 Electronic thermal overload monitoring

When the electronic thermal overload monitoring function (d104) is selected, the inverter displays the electronic thermal overload. If the electronic thermal overload exceeds 100%, the inverter will trip because of the overload protection (error code "E05").

(Display)

0.0 to 100.0 in steps of 0.1%

Related code

d103: BRD load factor monitoring

b090: Dynamic braking usage ratio

Related code

d104: Electronic thermal overload monitoring