b003: Retry wait time before motor restart
b007: Restart frequency threshold
C102: Reset mode selection
C103: Restart mode after reset
C001 to C008: Terminal [1] to [8] functions

Chapter 4 Explanation of Functions

Timing chart for switching from the inverter to the

commercial power supply

Timing chart for switching from the commercial power

supply to the inverter

MC1 ON

MC2

ON

MC3 ON

FW ON

CS

ON

Inverter output

frequency Operation

MC1

MC2

MC3

FW

CS

Inverter output frequency

ON

Duration of the interlock of MC2 and

MC3 (0.5 to 1 second)

ON

ON OFF

Retry wait time (b003) 0.5 to 1 second

Operation

4.2.49 Reset (RS) function

Starting with matching frequency

The reset function allows you to recover the inverter from a tripped state.

To perform resetting, press the STOP/RESET key of the digital operator or turn the RS terminal off.

To use the control circuit terminal for resetting, assign function "18" (RS) to an intelligent input terminal.

You can select the restart mode to apply after resetting with the restart mode after reset (C103). When C102 =03, starting with 0 Hz is selected regardless to C103 setting.

If the inverter trips because of overcurrent when it starts the motor with matching frequency, increase the retry wait time before motor restart (b003).

You can select the alarm reset timing with the reset mode selection (C102). You can also enable the reset signal to be output only when resetting an error alarm.

The RS terminal can be configured only as an a-contact (NO).

Do not use the RS terminal for the purpose of shutting off the inverter output. The reset operation clears the electronic thermal and BRD counter data stored in the inverter, and, without this data, the inverter may be damaged during operation.

Item

Function

Data or range of

Description

code

data

 

 

Retry wait time

 

 

(See the explanations of the retry after instantaneous power

b003

0.3 to 100. (s)

failure or the retry after trip due to insufficient voltage.)

before motor restart

 

 

Time to wait after reset until restarting the motor

 

 

 

Restart frequency

b007

0.00 to 400.0 (Hz)

(See the explanations of the retry after instantaneous power

threshold

failure or the retry after trip due to insufficient voltage.)

 

 

 

 

 

Resetting the trip when the RS signal is turned on (See

 

 

00

example 1.)

 

 

(When operation is normal) Shutting off the inverter output

 

 

 

 

 

 

(When an error has occurred) Resetting the trip

 

 

 

Resetting the trip when the RS signal is turned off (See

 

 

01

example 2.)

 

 

(When operation is normal) Shutting off the inverter output

Reset mode

 

 

C102

 

(When an error has occurred) Resetting the trip

selection

 

Resetting the trip when the RS signal is turned on (See

 

 

 

 

02

example 1.)

 

 

(When operation is normal) Disabling the inverter output

 

 

 

 

 

 

(When an error has occurred) Resetting the trip

 

 

 

Trip is reset (See example 1)

 

 

03

Internal data is not reset. (see 4.3.13)

 

 

(When operation is normal) Disabling the inverter output

 

 

 

 

 

 

(When an error has occurred) Resetting the trip

Restart mode after

C103

00

Start with 0 Hz

01

Start with matching frequency (See example 3.)

reset

 

02

Restart with input frequency (See example 4.)

 

 

4 - 54