Related code
b027: Overcurrent suppression enable

Chapter 4 Explanation of Functions

(2) Overload nitice function

The overload notice function allows you to make the inverter output an overload notice signal before tripping because of overload.

You can use this function effectively to prevent the machine (e.g., a conveyor)driven by the inverter from being overloaded and prevent the conveyor from being stopped by the overload protection of the inverter. To use this function, assign function "03" (OK) or "26" (OL2) to one of the intelligent output terminals [11] to

[15](C021 to C025) and the alarm relay terminal (C026). (Two types of overload notice signal are available for output.)

Item

Function code

Data or range of data

Description

Overload signal output

C040

00

Enabling the warning output during

acceleration, deceleration, and constant

mode

 

 

01

Enabling the warning output during constant

 

 

 

 

0.0

Disabling the warning output

Overload level setting

C041

0.1 to "2.0 x rated

Specifying the current at which to output the

OL signal (overload notice advance signal

 

 

current" (A)

 

 

(1))

 

 

 

 

 

0.0

Disabling the warning output

Overload setting (2)

C111

0.1 to "2.0 x rated

Specifying the current at which to output the

OL2 signal (overload notice advance signal

 

 

current" (A)

 

 

(2))

 

 

 

Overload restriction setting b022/b025

Overload level setting

C041/C111

Output current

OL/OL2 output

4.2.31 Overcurrent restraint

The overcurrent restraint function allows you to restrain the overcurrent that can occur when the output current sharply increases because of rapid acceleration.

You can enable or disable the function by setting the overcurrent suppression enable (b027).

Item

Function code

Data or range of data

Description

Overcurrent

b027

00

Disabling the overcurrent restraint

suppression enable

01

Enabling the overcurrent restraint

 

Note: When using the inverter for a lift, disable the overcurrent restraint function. If the overcurrent restraint functions during the lift operation, the lift may slide down because of insufficient torque.

4 - 40

Page 98
Image 98
Hitachi SJ700-2 instruction manual Overcurrent restraint