Related code
C031 to C035: Terminal [11] to [15] active state
C036: Alarm relay active state

Chapter 4 Explanation of Functions

Data

Description

Reference item

Page

53

MJA: Major failure

Major failure signal

4-70

54

WCO

 

4-71

55

WCOI

Window comparators function

56

WCO

 

 

4.2.59 Intelligent output terminal a/b (NO/NC) selection

The intelligent output terminal a/b (NO/NC) selection function allows you to specify a-contact or b-contact output for each of the intelligent output terminals [11] to [15] and the alarm relay terminal.

The intelligent output terminals [11] to [15] are used for open-collector output, and the alarm relay terminal is used for relay output.

Item

Function code

Terminal active state

C031 to C035

 

 

Alarm relay active state

C036

 

 

Data

00

01

00

01

Description

a-contact (NO)

b-contact (NC)

a-contact (NO)

b-contact (NC)

-An a-contact turns on the output signal when closed and turns it off when opened.

-A b-contact turns on the output signal when opened and turns it off when closed.

(1) Specifications of intelligent output terminals [11] to [15]

Intelligent output terminals [11] to [15] have the following specifications:

Inside the inverter

15

CM2

… …

11

Setting of C031 to C035

Power supply

Output signal

 

 

 

 

 

 

Electric characteristics

00

ON

ON

OFF

 

(Between each terminal and CM2)

(a-contact)

 

 

OFF

 

Voltage drop when turned on: 4 V or less

 

 

01

ON

ON

 

Allowable maximum voltage: 27 VDC

OFF

 

Allowable maximum current: 50 mA

(b-contact)

 

 

OFF

 

 

 

 

 

 

 

(2) Specifications of alarm relay terminal

The alarm relay terminal uses a normally-closed (NC) contact that operates as described below.

Inside the inverter

AL0

AL1 AL2

Example of operation as an alarm output terminal

Setting

Power

Inverter

Output terminal state

 

 

 

of C036

supply

status

AL1-AL0

AL2-AL0

 

 

Maximum contact

 

ON

Error

Closed

Open

 

AL1-AL0

capacity

00

 

 

 

 

Minimum contact

Normal

Open

Closed

 

 

 

 

OFF

Open

Closed

 

 

capacity

 

 

 

 

 

 

 

Maximum contact

01

ON

Error

Open

Closed

 

 

 

 

capacity

Normal

Closed

Open

 

AL2-AL0

(default)

 

 

Minimum contact

OFF

Open

Closed

 

 

 

 

 

capacity

 

 

 

 

 

 

 

Resistance load

Inductive load

250 VAC, 2 A

250 VAC, 2 A

30 VDC, 3 A

30 VDC, 8 A

100 V AC, 10 mA

5 VDC, 100 mA

250 VAC, 1A

250 VAC, 0.2 A

30 VDC, 1A

30 VDC, 0.2 A

100 VAC, 10 mA

5 VDC, 100 mA

4 - 61

Page 119
Image 119
Hitachi SJ700-2 Intelligent output terminal a/b NO/NC selection, Example of operation as an alarm output terminal