Hitachi SJ700-2 Actual-frequency monitoring, Torque command monitoring, Torque bias monitoring

Models: SJ700-2

1 274
Download 274 pages 15.86 Kb
Page 61
Image 61
Related code
d014: Power monitoring
Related code d013: Output voltage monitoring

Chapter 4 Explanation of Functions

4.1.8 Actual-frequency monitoring

The actual-frequency monitoring function is effective only when a motor equipped with an encoder is connected to the inverter and the feedback option board (SJ-FB) is mounted in the inverter. When the actual-frequency monitoring function (d008) is selected, the inverter displays the actual operating frequency of the motor (regardless of the motor control method (A044 or A244)).

Related code

d008: Actual-frequency monitoring

P011: Encoder pulse-per-revolution (PPR) setting

H004: Motor poles setting, 1st motor

H204: Motor poles setting, 2nd motor

(Display)

Forward operation:

0.00to 99.99 in steps of 0.01 Hz

100.0to 400.0 in steps of 0.1 Hz

Reverse operation:

-0.0 to -99.9 in steps of 0.1 Hz

-100 to -400 in steps of 1 Hz

Note: To use this monitoring function, set the encoder pulse-per-revolution (PPR) setting (P011) and the number of motor poles (H004 or H204) correctly.

4.1.9 Torque command monitoring

Related code

 

The torque command monitoring function is effective when you have

d009: Torque command

monitoring

P033: Torque command input selection

selected control by torque for the vector control with sensor. When the

P034: Torque command setting

torque command monitoring function (d009) is selected, the inverter

A044: V/f characteristic curve selectcion

displays the value of the currently input torque command.

C001 to C008: Terminal [1] to [8]

 

 

The % monitor lamp lights up while the inverter is displaying the torque command value. Assign 52 (ATR) on intelligent input terminal and turn on to activate torque control.

(Display)

0. to 200. in steps of 1 %

4.1.10 Torque bias monitoring

 

Related code

 

The torque bias monitoring function is effective when you have selected

d010: Torque bias monitoring

A044: V/f characteristic curve selectcion

the vector control with sensor. When the torque bias monitoring function

P036: Torque bias mode

(d010) is selected, the inverter displays the value of the currently set

P037: Torque bias value

value of torque bias.

P038: Torque bias polarity

The % monitor lamp lights up while the inverter is displaying the torque bias value.

(Display)

 

 

 

-150. to +150. in steps of 1 %

 

 

 

4.1.11 Torque monitoring

 

Related code

 

 

 

 

When the torque monitoring function (d012) is selected, the inverter

d012: Torque monitoring

 

displays the estimated value of the torque output from the inverter.

A044: V/f characteristic curve selectcion

The % monitor lamp lights up while the inverter is displaying the estimated output torque.

(Display)

-300. to +300. in steps of 1 %

Note: This monitoring function is effective only when you have selected the sensorless vector control, 0Hz-range sensorless vector control, or vector control with sensor as the control mode.

Displayed value is not accurate when the other control method is selected.

4.1.12 Output voltage monitoring

When the output voltage monitoring function (d013) is selected, the inverter displays the voltage output from the inverter.

The V monitor lamp lights up while the inverter is displaying the output voltage.

(Display)

0.0 to 600.0 in steps of 0.1 V

(remark) Displayed value may not be accurate when the output voltage is differ from input voltage.

4.1.13 Power monitoring

When the power monitoring function (d014) is selected, the inverter displays the electric power (momentary value) input to the inverter.

The kW monitor lamps (V and A lamps) light up while the inverter is displaying the input power.

(Display)

0.0 to 999.9 in steps of 0.1 kW

4 - 3

Page 61
Image 61
Hitachi SJ700-2 Actual-frequency monitoring, Torque command monitoring, Torque bias monitoring, Torque monitoring