Chapter 4 Explanation of Functions

4.2.42 Jogging (JG) command setting

The jogging command setting function allows you to set and finely tune the motor-stopping position.

To use this function, assign function "06" (JG) to an intelligent input terminal.

(1) Jog frequency setting

JG

FW

RV

Output frequency

A038

Related code

A038: Jog frequency setting

A039: Jog stop mode

C001 to C008: Terminal [1] to [8] functions

Since the inverter operates the motor with a full voltage for the jogging operation, the inverter can easily trip during the latter. Adjust the jog frequency setting (A038) properly so that the inverter will not trip.

Item

Function code

Range of data

Description

Jog frequency

A038

0.0 or "start frequency"

Setting of the frequency to output during jogging

setting

to 9.99 (Hz)

operation

 

(2) Jog stop mode

Item

Function code

Data

Description

 

 

00

Disabling jogging while the motor is operating and

 

 

enabling free-running when the motor is stopped

 

 

 

 

 

01

Disabling jogging while the motor is operating and

 

 

enabling stopping after deceleration when the

 

 

 

motor is stopped

 

 

02 (See Note 2.)

Disabling jogging while the motor is operating and

Jog stop mode

A039

enabling DC braking when the motor is stopped

 

03

Enabling jogging while the motor is operating and

 

 

 

 

enabling free-running when the motor is stopped

 

 

 

 

 

04

Enabling jogging while the motor is operating and

 

 

enabling stopping after deceleration when the

 

 

 

motor is stopped

 

 

05 (See Note 2.)

Enabling jogging while the motor is operating and

 

 

enabling DC braking when the motor is stopped

 

 

 

Note 1: To perform the jogging operation, always turn on the JG terminal before turning on the FW or RV terminals. (Follow this sequence of command inputs also when using the digital operator to enter operation commands.)

(Example 1)

(Example 2)

JG

FW

Output frequency

JG

 

 

FW

 

Deceleration

Normal

Jogging operation

 

 

operation

 

 

Output

 

 

frequency

Free running

 

Acceleration according to the setting of "b088"

When "00", "01", or "02" is specified for the jog stop mode (A039), the jogging operation will not be performed if the FW signal is turned on earlier than the JG signal.

When "03", "04", or "05" is specified for the jog stop mode (A039), the jogging operation will be performed, even if the FW signal is turned on earlier than the JG signal. However, the motor will stop after free-running if the JG signal is turned off earlier than the FW signal.

Note 2: You must set DC braking data if you specify "02" or "05" for the jog stop mode (A039). (See Section 4.2.19.)