Chapter 4 Explanation of Functions

Register

Function name

Function code

R/W

Monitoring and setting items Data

Register

No.

resolution

No.

 

 

 

 

 

 

 

0 (0 pole), 1 (2 poles), 2 (4 poles), 3 (6

 

 

 

 

 

poles), 4 (8 poles), 5 (10 poles), 6 (12

 

 

 

 

 

poles), 7 (14 poles), 8 (16 poles), 9 (18

-

1633h

Motor poles setting for RPM

P049

R/W

poles), 10 (20 poles), 11 (22 poles), 12

 

 

 

 

(24 poles), 13 (26 poles), 14 (28 poles),

 

 

 

 

 

15 (30 poles), 16 (32 poles), 17 (34

 

 

 

 

 

poles), 18 (36 poles), 19 (38 poles)

 

1634h to

(Reserved)

-

-

Inaccessible

-

1638h

 

 

 

 

 

1639h

Pulse train frequency scale

P055

R/W

10 to 500 (input frequency corresponding

0.1 [kHz]

to the allowable maximum frequency)

163Ah

Time constant of pulse train frequency

P056

R/W

1 to 200

0.01 [sec.]

filter

 

 

 

 

 

163Bh

Pulse train frequency bias

P057

R/W

-100 to +100

1 [%]

163Ch

Pulse train frequency limit

P058

R/W

0 to 100

1 [%]

163Dh

(Reserved)

-

-

Inaccessible

-

163Eh

Multistage position setting 0

P060(HIGH)

R/W

 

1

163Fh

P060(LOW)

R/W

 

 

 

 

1640h

Multistage position setting 1

P061(HIGH)

R/W

 

1

1641h

P061(LOW)

R/W

 

 

 

 

1642h

Multistage position setting 2

P062(HIGH)

R/W

 

1

1643h

P062(LOW)

R/W

 

 

 

 

1644h

Multistage position setting 3

P063(HIGH)

R/W

 

1

1645h

P063(LOW)

R/W

 

 

 

 

1646h

Multistage position setting 4

P064(HIGH)

R/W

 

1

1647h

P064(LOW)

R/W

 

 

 

 

1648h

Multistage position setting 5

P065(HIGH)

R/W

 

1

1649h

P065(LOW)

R/W

 

 

 

 

164Ah

Multistage position setting 6

P066(HIGH)

R/W

 

1

164Bh

P066(LOW)

R/W

 

 

 

 

164Ch

Multistage position setting 7

P067(HIGH)

R/W

 

1

164Dh

P067(LOW)

R/W

 

 

 

 

164Eh

Zero-return mode selection

P068

R/W

0(Low) / 1(High1) / 2(High2)

 

164Fh

Zero-return direction selection

P069

R/W

0(FW) / 1(RV)

 

1650h

Low-speed zero-return frequency

P070

R/W

0 to 1000

 

1651h

High-speed zero-return frequency

P071

R/W

0 to 40000

 

1652h

Position range specification (forward)

P072(HIGH)

R/W

0 to 536870912 (when P012 = 2) /

1

1653h

P072(LOW)

R/W

0 to 2147483647 (when P012 = 3)

 

 

1654h

Position range specification (reverse)

P073(HIGH)

R/W

-536870912 to 0 (when P012 = 2) /

1

1655h

P073(LOW)

R/W

-2147483647 to 0 (when P012 = 3)

 

 

1656h to

(Reserved)

-

-

Inaccessible

-

1665h

 

 

 

 

 

1666h

Easy sequence user parameter U (00)

P100

R/W

0 to 65530

1

1667h

Easy sequence user parameter U (01)

P101

R/W

0 to65530

1

1668h

Easy sequence user parameter U (02)

P102

R/W

0 to 65530

1

1669h

Easy sequence user parameter U (03)

P103

R/W

0 to 65530

1

166Ah

Easy sequence user parameter U (04)

P104

R/W

0 to 65530

1

166Bh

Easy sequence user parameter U (05)

P105

R/W

0 to 65530

1

166Ch

Easy sequence user parameter U (06)

P106

R/W

0 to 65530

1

166Dh

Easy sequence user parameter U (07)

P107

R/W

0 to 65530

1

166Eh

Easy sequence user parameter U (08)

P108

R/W

0 to 65530

1

166Fh

Easy sequence user parameter U (09)

P109

R/W

0 to 65530

1

1670h

Easy sequence user parameter U (10)

P110

R/W

0 to 65530

1

1671h

Easy sequence user parameter U (11)

P111

R/W

0 to 65530

1

1672h

Easy sequence user parameter U (12)

P112

R/W

0 to 65530

1

1673h

Easy sequence user parameter U (13)

P113

R/W

0 to 65530

1

1674h

Easy sequence user parameter U (14)

P114

R/W

0 to 65530

1

1675h

Easy sequence user parameter U (15)

P115

R/W

0 to 65530

1

1676h

Easy sequence user parameter U (16)

P116

R/W

0 to 65530

1

1677h

Easy sequence user parameter U (17)

P117

R/W

0 to 65530

1

1678h

Easy sequence user parameter U (18)

P118

R/W

0 to 65530

1

1679h

Easy sequence user parameter U (19)

P119

R/W

0 to 65530

1

167Ah

Easy sequence user parameter U (20)

P120

R/W

0 to 65530

1

167Bh

Easy sequence user parameter U (21)

P121

R/W

0 to 65530

1

167Ch

Easy sequence user parameter U (22)

P122

R/W

0 to 65530

1

167Dh

Easy sequence user parameter U (23)

P123

R/W

0 to 65530

1

167Eh

Easy sequence user parameter U (24)

P124

R/W

0 to 65530

1

167Fh

Easy sequence user parameter U (25)

P125

R/W

0 to 65530

1

4 - 158

Page 216
Image 216
Hitachi SJ700-2 instruction manual To the allowable maximum frequency