Chapter 4 Explanation of Functions

(b) Constant-torque characteristic

Make this setting when driving a constant-torque motor with the inverter.

(Example) Setting on the SJ700-150LF (rated current: 64 A) When "b012" is 64 A, and output frequency is 2.5 Hz:

Reduction

Trip time (s)

scale

 

X1.0

X0.9

X0.8

 

 

 

 

Inverter output

0

2.5

5

60

frequency (Hz)

 

60

3.0

062.8 86.4 115.2

(98.1%)(135%) (180%)

Motor current (A) (Ratio to the rated current of inverter)

(c) Free setting of electronic thermal characteristic

To protect the motor against overheating, you can set the electronic thermal characteristic freely according to the load on the motor.

The range of setting is shown in the figures below.

Item

Function code

Range of data

Description

Free setting, electronic

b015/b017/

 

 

thermal frequency (1) (2)

0. to 400. (Hz)

Setting of frequency at each breakpoint

b019

(3)

 

 

 

 

 

Free setting, electronic

b016/b018/

0.0 (A)

Disabling the electronic thermal protection

0.1 to rated

 

thermal current (1) (2) (3)

b020

Setting of the current at each breakpoint

current. (A)

 

 

 

X1.0

X0.8

Range of

 

setting

 

 

 

 

 

Inverter output

0 5

40

frequency (Hz)

(Example) When the output frequency is equal to the setting of "b017"

Trip time (s)

60

3.0

0

(x) (y)

(z)

Output current (A)

b020

b018

b016

0b01 b017 b019 A004/A204/A304

Maximum frequency (Hz)

(x): ("setting of b018"/"rated current") x 109%

(y): ("setting of b018"/"rated current") x 150%

(z): ("setting of b018"/"rated current") x 200%

(3) Thermal warning

You can configure this function so that the inverter outputs a warning signal before the electronic thermal protection operates against motor overheat. You can also set the threshold level to output a warning signal with the electronic thermal warning level setting (C061).

To output the warning signal, assign function "13" (THM) to one of the intelligent output terminals [11] to [15] (C021 to C025) and the alarm relay terminal (C026).

Item

Function code

Data

Description

Electronic thermal

C061

0.

Disabling the warning output

 

Setting of the threshold level to output the

warning level setting

1. to 100. (%) (*1)

 

thermal warning signal

 

 

 

*1 Set the ratio (%) of the warning level to the integrated value of the electronic thermal characteristic. A setting of 100% corresponds to the inverter trip due to overload (error code "E05").