Hitachi SJ700-2 instruction manual Communication Functions, Communication specifications

Models: SJ700-2

1 274
Download 274 pages 15.86 Kb
Page 171
Image 171

Chapter 4 Explanation of Functions

4.4 Communication Functions

The inverter can engage in RS485 communications with an external control system that is connected to the TM2 terminal block (on the control circuit terminal block board) of the inverter. The SJ700 series inverter shares the ASCII communication protocol with the SJ300 and L300P series inverters.

Related code

A001: Frequency source setting

A002: Run command source setting

C071: Communication speed selection

C072: Node allocation

C073: Communication data length selection

C074: Communication parity selection

C075: Communication stop bit selection

C078: Communication wait time

C079: Communication mode selection

(1) Communication specifications

Item

ASCII mode

Modbus-RTU mode

Remarks

Transmission speed

2,400, 4,800, 9,600, or 19,200 bps

Selection with the digital operator

Communication method

Half-duplex communication

 

Synchronization method

Start-stop transmission

Asynchronous

 

transmission

 

 

 

 

Transmission code

ASCII code

Binary code

 

Transmission method

Transmission beginning

with the lowest-order bit

 

Applicable interface

RS485

 

Data bit length

7 or 8 bits

8 bits

Selection with the digital operator

Parity

No parity, even parity, or odd parity

Selection with the digital operator

Stop bit length

1 or 2 bits

Selection with the digital operator

Initiation method

Initiation only by a command from the external

 

control system

 

 

 

Waiting time

10 to 1,000 ms

0 to 1,000 ms

Setting with the digital operator

Connection format

1-to-N connection (N: Maximum of 32 [inverters])

Station number to be selected

with the digital operator

 

 

 

 

Overrun, framing, BCC,

Overrun, framing,

 

Error check

vertical parity, and

CRC-16, and

 

 

longitudinal parity errors

longitudinal parity errors

 

<Specifications and connections of RS485 ports>

For the RS485 communication function, use the TM2 terminal block on the control circuit terminal block board.

 

Abbreviated

 

 

name of

Description

Control circuit block

terminal

 

SP

Positive signal terminal

 

for transmission

 

 

 

SN

Negative signal terminal

 

for transmission

 

 

 

RP

Terminal to enable the

 

terminating resistor

 

 

Control circuit

SN

Terminal to enable the

 

terminating resistor

block board

 

 

 

4 - 113

Page 171
Image 171
Hitachi SJ700-2 instruction manual Communication Functions, Communication specifications