Related code
b098: Thermistor for thermal protection control
b099: Thermal protection level setting
C085: Thermistor input tuning
Related code
C160 to C167: Response time of intelligent input terminals 1 to 8
C168: FW terminal response time

Chapter 4 Explanation of Functions

4.2.78 Output signal delay/hold function

The output signal delay/hold function allows you to set on-delay and off-delay times for each output terminal.

Since every output signal is turned on or off immediately when the relevant condition is satisfied, signal chattering may occur if signal outputs conflict with each other. Use this function to avoid such a problem by holding or delaying specific signal outputs. To use this function, set on-delay and off-delay times for individual output terminals (a total of six terminals, such as intelligent output terminals [11] to [15] and the alarm relay terminal).

Output terminal

On-delay time

Off-delay time

11

C130

C131

12

C132

C133

13

C134

C135

14

C136

C137

15

C138

C139

RY(AL*)

C140

C141

Related code

C130: Output 11 on-delay time

C131: Output 11 off-delay time

C132: Output 12 on-delay time

C133: Output 12 off-delay time

C134: Output 13 on-delay time

C135: Output 13 off-delay time

C136: Output 14 on-delay time

C137: Output 14 off-delay time

C138: Output 15 on-delay time

C139: Output 15 off-delay time

C140: Output RY on-delay time

C141: Output RY off-delay time

Item

Function code

Range of data

Description

Output on

C130/C132/C134/

0.0 to 100.0 (s)

Setting of on

C136/C138/C140

 

 

 

Output off

C131/C133/C135/

0.0 to 100.0 (s)

Setting of off

C137/C139/C141

 

 

 

4.2.79 Input terminal response time

- The input terminal response time function allows you to specify a sampling time for each of intelligent input terminals 1 to 8 and the FW terminal. You can use this function effectively to remove noise (e.g., chattering).

-If chattering hinders constant input from an input terminal, increase the response time setting for the input terminal. Note that an increase in response time deteriorates the response. The response time can be set in a range of about 2 to 400 ms (corresponding to settings of 0 to 200).

Item

Function code

Range of data

Description

Response time of intelligent

C160-C167

0. to 200.

Variable in step of 1

input terminals 1 to 8

 

FW terminal response time

C168

 

 

4.2.80 External thermistor function (TH)

The external thermistor function allows you to connect an external thermistor installed in external equipment (e.g., motor) to the inverter,

and use the thermistor for the thermal protection of the external equipment. Connect the external thermistor to control circuit terminals TH and CM1.

Make the functional settings according to the thermistor specifications as described below.

When using this function, the wiring distance between the inverter and motor must be 20 m or less. Since the thermistor current is weak, isolate the thermistor wiring to the inverter from other wirings appropriately to prevent the thermistor signal from being affected by the noise caused by other signal currents, including the motor current.

Item

Function code

Range of data

Description

 

 

00

Disabling the external thermistor (TH) function

Thermistor for thermal

b098

01

Enabling the TH function (resistor element with

a positive temperature coefficient [PTC])

protection control

 

 

02

Enabling the TH function (resistor element with

 

 

 

 

a negative temperature coefficient [NTC])

 

 

 

Thermal protection level

 

 

Setting of the thermal resistance level

b099

0 to 9999. (Ω)

(according to the thermistor specifications) at

setting

 

 

which to trigger tripping

 

 

 

Thermistor input tuning

C085

0.0 to 1000.

Setting for gain adjustment

Note: Specifying "01" for the thermistor for thermal protection control (b098) without an external thermistor connected makes the inverter trip.

4 - 72

Page 130
Image 130
Hitachi SJ700-2 Output signal delay/hold function, Input terminal response time, External thermistor function TH