Related code b082: Start frequency adjustment

Chapter 4 Explanation of Functions

4.2.33 Start frequency setting

The start frequency setting function allows you to specify the inverter output frequency that the inverter initially outputs when an operation command is input.

Use this function mainly to adjust the start torque.

If the start frequency (b082) is set too high, the inverter will start the motor with a full voltage, which will increase the start current. Such status may trigger the overload restriction operation or make the inverter prone to easily tripping because of the overcurrent protection.

Specifying "04" (0SLV: 0Hz-range sensorless vector control) or "05" (V2: vector control with sensor) for the V/F characteristic curve selection (A044) disables the start frequency setting function.

Item

Function code

Range of data

Description

Start frequency

b082

0.10 to 9.99 (Hz)

Setting of the start frequency

adjustment

 

 

 

FW

b082

Output frequency

Output voltage

4.2.34 Reduced voltage start function

The reduced voltage start function enables you to make the inverter increase the output voltage gradually when starting the motor.

Set a small value for the reduced voltage start selection (b036) if you intend to increase the start torque. On the other hand, setting a small value will cause the inverter to perform full-voltage starting and to easily trip because of overcurrent.

Related code

b036: Reduced voltage start selection

b082: Start frequency adjustment

Item

Function code

 

Range of data

 

Description

Reduced voltage start

 

 

00

Disabling the reduced voltage starting

b036

 

 

01: Short (about 6 ms)

selection

 

01 to 255

 

 

 

 

 

255: Long (about 1.53 s)

 

 

 

 

 

 

FW

 

 

 

 

 

 

 

 

 

 

 

Start frequency b082

Output frequency

Output voltage

 

 

 

 

 

 

Reduced Voltage Start

00

01 ・・・ 06

b036

 

 

4 - 42