Hitachi SJ700-2 instruction manual Initialization setting

Models: SJ700-2

1 274
Download 274 pages 15.86 Kb
Page 133
Image 133
Related code
b084: Initialization mode (parameters or trip history)
b085: Country code for initialization
Chapter 4 Explanation of Functions

4.2.83 Initialization setting

The initialization function allows you to initialize the adjusted settings on the inverter to restore the factory settings. You can also clear the trip history data alone.

The settings of initialization are described below.

The settings of "P100" to "P131", running-time data, and power-on time data cannot be cleared.

Item

Function code

Data

Description

Initialization mode

 

00

Clearing on the trip history data

 

01

Initializing only the settings

(parameters or trip

b084

The factory settings are restored.

 

history)

 

 

 

 

02

Clearing the trip history data and initializing the

 

 

settings

 

 

 

Country code for

b085

00

Defaults intended for Japan

01

Defaults intended for Europe

initialization

 

02

Defaults intended for the U.S.A.

 

 

(Initializing procedure)

Adjust the above settings as required, and then perform the following procedure:

RUN

STOP/

RUN

STOP/

RUN

STOP/

 

RESET

 

RESET

 

RESET

FUNC

STR

FUNC

STR

FUNC

STR

1) Holding down the FUNC and [2]

2) Initialization is in progress.

3) When the initialization is

(down) keys, press and hold down

- The above figure shows the

completed, the monitor displays

the STOP/RESET key.

monitor display (indicating that the

code "d001".

- After the monitor starts blinking,

initialization is in progress)

Confirm that the settings have

release only the STOP/RESET

intended for Japan. Those

been initialized.

key. (The display on the monitor

intended for other regions and trip

 

changes to that shown in the

history clearance are shown

 

middle figure above.

below.

 

- Release the FUNC and [2]

 

 

(down) keys.

 

 

Initialization-in-progress

 

 

display intended for Europe

 

 

Initialization-in-progress display intended for the U.S.A.

Initialization-in-progress display for trip history clearance

In the far-left digit, the lighting segments move round for

Note 1: The initialization operation does not initialize the analog input settings (C081, C082, C083, C121, C122, and C123) and thermistor coefficient setting (C085).

Note 2: The initialization operation does not initialize the settings of easy sequence user parameters (P100 to P131).

4 - 75

Page 133
Image 133
Hitachi SJ700-2 instruction manual Initialization setting