AT&T 3.0 manual Environment

Models: 3.0

1 608
Download 608 pages 29.49 Kb
Page 33
Image 33

Overview

The following sections provide detailed instructions for these installation procedures. Follow the procedures in the order in which they are presented.

Environment

The control unit must be installed on a backboard. The placement of the backboard, and the control unit on it, requires careful consideration. Make sure you install the backboard in an area that meets all of the environmental requirements listed in Table 2–1.

Table 2-1. Environmental Requirements

Operating

4 00-104°F (4°-400C )

Temperatures

Optimal temperature: 60°F(15.6°C)

 

 

Humidity

20%–80%

 

 

Airborne

Do not expose the control unit to moisture, corrosive gases, dust,

Contamination

chemicals, spray paint, or similar material.

 

 

Ventilation

Allow at least 1 in. (2.54 cm) on the right and left sides of the control

 

unit and 12 in. (30.48 cm) minimum, above and below it, to prevent

 

overheating,

 

Do not place the control unit near extreme heat sources (for example:

 

furnaces, heaters, attics, or direct sunlight).

 

Electrical Fields Do not expose the control unit to devices that generate electrical

 

currents causing interference (such as arc welders or motors).

 

 

Heat Dissipation

Basic carrier: 500 Btu/hr

 

Basic carrier: with one expansion carrier 1000 Btu/hr

 

Basic carrier: with two expansion carriers 1500 Btu/hr

WARNING:

Do not install the control unit outdoors.

2-2Installing the Control Unit

Page 33
Image 33
AT&T 3.0 manual Environment