AT&T 3.0 manual Unplug the circuit tester, Measuring the AC Outlet Voltages

Models: 3.0

1 608
Download 608 pages 29.49 Kb
Page 40
Image 40

AC Power and Grounding

If the circuit is properly grounded, the ye low and white lights on the tester turn on.

2 Unplug the circuit tester.

Using a Volt-Ohm Milliammeter (VOM)

1 Set the VOM to the lowest scale on which you can read 130 V AC.

2Measure the AC outlet voltages. See Figure 2-2.

Phase to ground should be 110 to 125 V AC.

Neutral to ground should be less than 1 V AC.

Phase to neutral should be 110 to 125 V AC.

110-125 / Volts AC\

Phase

Neutral ( H O T )

 

Ground

Less than

110 - 125

1.0 Volt AC

Volts AC

 

 

 

Figure 2-2. Measuring the AC Outlet Voltages

WARNING:

If the voltage readings do not measure the values required, the AC outlet is improperly wired- do not install the system. Advise the customer to have a licensed electrician correct the problem.

Installing the Control Unit 2-9

Page 40
Image 40
AT&T 3.0 manual Unplug the circuit tester, Measuring the AC Outlet Voltages