100D Module Problems

If the test fails, find the error message in Table 4-6 and proceed as indicated.

Table 4-6. Internal Loopback Test Errors

 

 

Error Messages

Corrective Action

 

 

Slot is not busied-out

Exit the test, busy-out the slot, and try again.

 

 

 

 

 

 

 

 

 

Slot empty or not valid

Exit the test and try again; be sure to type the correct

 

 

 

slot number. Do not indicate an empty slot or the

 

 

 

processor (00).

 

 

 

 

 

 

 

 

 

FMWR not in Standby Node

Exit the test and try again; if this error persists, record

 

 

 

the errors on the repair tag and replace the module

 

 

 

being tested.

 

 

 

 

 

 

 

 

Test running too long

Exit the test and try again; if this error persists, record

 

 

 

the errors on the repair tag and replace the module

 

 

 

being tested.

 

 

 

 

 

 

 

 

Not in TEST/STANDBY mode

Exit the test and try again; if this error persists, record

 

 

 

the errors on the repair tag and replace the module

 

 

 

being tested.

 

 

 

 

 

 

Any errors on the CSU-lpbk Failed

Check the cable between the 100D module and the

screen

CSU; then retest. If the problem persists, check the

 

 

 

CSU settings.

 

 

 

Exit the test and try again; if this error persists, record

 

 

 

the errors on the repair tag and replace the module

 

 

 

being tested.

 

 

 

 

Any other error

Record the errors on the repair tag and replace the

 

 

 

module; if in doubt, escalate to your technical support

 

 

 

organization.

 

 

 

 

 

 

 