APPENDICES

APPENDIX 1.2 Minor errors

These errors are detected in the PLC program or servo program, and the error codes of 1 to 999 are used.

Minor errors include the setting data errors, starting errors, positioning control errors and current value/speed change errors and system errors.

(1) Setting data errors (1 to 99)

These errors occur when the data set in the parameters for positioning control is not correct.

The error codes, causes, processing, and corrective actions are shown in Table 1.3.

Table 1.3 Setting data error (1 to 99) list

Error

Erroneous

Check timing

Error cause

Error

Corrective action

code

data

processing

 

 

 

 

 

Home position return start

The home position address is

 

Set the home position address

 

 

of the count, proximity

outside the range of 0 to

 

within the setting range using a

21

 

dog, data set, dog cradle,

35999999 ( 10–5[degree]) with

 

peripheral device.

 

 

stopper and limit switch

degree axis.

 

 

 

 

combined type

 

 

 

 

 

Home position return start

The home position return speed

 

Set the home position return speed

22

 

is outside the range of 1 to

 

or less to the speed limit value

 

 

of the count, proximity

speed limit value.

 

using a peripheral device.

 

 

dog, dog cradle, stopper

 

 

 

The creep speed is outside the

 

Set the creep speed below to the

23

 

and limit switch combined

 

 

type

range of 1 to home position

 

home position return speed or less

 

 

return speed.

 

using a peripheral device.

 

 

 

 

 

Home

Home position return start

The travel value after the

Home position

Set the travel value after the

24

position

of the count type

proximity dog ON is outside the

return is not

proximity dog ON within the setting

 

return data

 

range of 0 to (231-1) ( unit).

started.

range using a peripheral device.

 

Home position return start

The parameter block No. is

Set the parameter block No. within

 

 

 

 

 

of the count, proximity

outside the range of 1 to 64.

 

the setting range using a peripheral

25

 

dog, dog cradle, stopper

 

 

device.

 

 

and limit switch combined

 

 

 

 

 

type

 

 

 

 

 

Home position return start

Torque limit value at the creep

 

Set the torque limit value at the

26

 

speed is outside the range of 1

 

creep speed within the setting

 

 

of the stopper type

to 1000[%].

 

range using a peripheral device.

 

 

 

 

 

 

Home position return start

Dwell time at the home position

 

Set the dwell time at the home

27

 

return is outside the range of 0

 

position return retry within the

 

of the usable retry

to 5000[ms].

 

setting range using a peripheral

 

 

function

 

 

 

 

 

device.

 

 

 

 

 

 

 

 

The interpolation control unit of

Control with the

Set the same control unit of the

40

Parameter

Interpolation control start

the parameter block is different

control unit of

fixed parameters and servo

block

from the control unit of the fixed

the fixed

parameters.

 

 

 

parameters.

parameters.

 

POINT

When the interpolation control unit of parameter block is different from the control unit of fixed parameters, an error code may not be stored with the combination of units.

Refer to Section 6.1.4 for details.

APP - 7