Ericsson LBI-39224 manual 1s. Corrective

Models: LBI-39224

1 330
Download 330 pages 24.07 Kb
Page 285
Image 285

 

 

 

 

 

 

 

 

LBI-39224

 

 

 

 

 

 

LOGGED

LOGGED

 

 

CAUSE/

 

ERROR

ERROR

 

 

CORRECTIVE

 

MESSAGE

 

DATA

 

 

ACTION

 

 

 

 

 

 

 

 

 

 

 

E05-021:

 

 

 

 

 

 

 

 

 

INCOMPATIBLE -

 

 

 

 

 

 

 

 

 

AUDIO BUS

 

 

 

 

 

 

 

 

 

E05-023:

 

 

 

 

 

 

 

 

 

INCOMPATIBLE -

 

 

 

 

 

 

 

 

 

CEC/IMC MANAGER

 

 

 

 

 

 

 

 

 

E06-116:

No

information

 

A Controller Board was installed

INVALID VALUE -

contained in the data

 

that conflicted with an existing

ASSIGNMENT

word.

 

 

 

Controller Board.

For example a

 

 

 

 

 

MIM 6 and a VMIM 6, or two CIM

 

 

 

 

 

1s. Corrective

Action:

Both

 

 

 

 

 

interface modules

that

are

 

 

 

 

 

conflicting will have this error

 

 

 

 

 

active.

Change

the

device

 

 

 

 

 

type/assignment

setting of the

 

 

 

 

 

board in error. All boards that

 

 

 

 

 

conflicted must be reset to clear the

 

 

 

 

 

error.

 

 

 

 

E07-119:

Lower

byte

of the

 

This Controller Board is set up to

INVALID

data

word contains

 

be an end node, but an end node

REDUNDANCY -

the node ID of the

 

already exists in the system.

This

MULTIPLE END

existing end

node.

 

message replaces warning W06-

NODES

Upper byte of the data

 

119

beginning

 

with

MOM

 

word is reserved.

 

Controller Board firmware version

 

 

 

 

 

3.00. Corrective Action: To clear

 

 

 

 

 

the error, only one (1) Controller

 

 

 

 

 

Board should have its end node

 

 

 

 

 

DIP switch set to the ON position.

A-5

Page 285
Image 285
Ericsson LBI-39224 manual 1s. Corrective