Install the 1145B1 Power Supply
32.The 1145B1 (not 1145A1) is required for installation outside the United States.
Auxiliary power (local or bulk) is always required in the following situations:
■Attendant console 302B.
■Any 8520 terminal.
■Any
■Any
■Any 8510 terminal in passive bus or with an asynchronous data module. (Provide auxiliary power to an 8510 unless you are certain it will never be used to support such applications as data or video.)
This section tells how to install the 1145B1 Power Supply, 1146B1 Power Distribution Unit, and 2.5 amp hour (AH)
Wall-Mounting Plates
Two wall mounting plates are provided for easy assembly and to provide correct spacing between units for cooling. The top plate is needed for mounting the
1.Locate one plate directly below the other one such that the AC power cord
NOTE:
A maximum of four Power Supplies can be powered from one dedicated 110VAC, 20 amp (or 230VAC, 15A) feeder. Use only unswitched receptacles. In other words, receptacles not connected to a wall switch.
2.Secure the wall mounting plates to a standard 3/4 inch (2 cm) thick plywood mounting board. Each mounting plate comes with four
Issue 1 September 1995