Install Generic 3 Management

6

Terminal

 

This chapter contains Generic 3 Management Terminal (G3-MT) requirements. Also detailed is:

How to directly connect a terminal to the switch

How to set up the terminal

Alternative procedure to remotely connect a terminal to the switch.

The Generic 3 Management Terminal (G3-MT) shipped with the system is a 715 Management Terminal (715 MT). See the documentation packed with the terminal for information not contained in this chapter.

Generic 3 Management Terminal

(G3-MT) Requirements

One Generic 3 Management Terminal (G3-MT) should be located in the same equipment room as the cabinet or in sight of the cabinet and must be within 50 feet (18 meters) of the cabinet. It is strongly recommended the terminal be connected directly to the switch cabinet with the shortest possible cable. If desired, another terminal can be connected remotely.

!CAUTION:

When the terminal is being installed to support a DC-powered system or a system requiring electromagnetic shielding, a 116A Electronic Industries Association (EIA) ground isolator (comcode 106 005 242) must be installed at the back of the switch cabinet as shown in the schematic in Figure 6-2and as described in this chapter.

Issue 1 September 1995 6-1

Page 85
Image 85