
Locate and Lay Out the Equipment Room
Power Arrangements for DC Power
The following table shows the input DC requirements for the system
Parameter | Requirements |
Static Voltage | |
| (measured at input to System cabinet) under normal |
| operating conditions. |
Dynamic | Transient change in voltage— +/- 5% of steady state |
Voltage | voltage. Allowed transient |
| milliseconds. |
AC Ripple | Maximum wideband AC ripple— 450 mvpp (mill ivolts peak- |
Voltage | |
Low Voltage | Automatic |
Disconnect | than |
Overvoltage | Input voltage at switching cabinets shall not exceed |
Protection | VDC. |
Voltage Drop | Maximum |
| feeder cables between the power board and the System |
| cabinet. Feeders must be Underwriter Laboratories (UL) |
| approved (or equivalent) and Canadian Safety Association |
| (CSA) certified. Recommended |
| Royal Electric #X4905 or equivalent No. 1 AWG is required |
| for distances up to 50 feet (15 meters). Cable resistance |
| must be equal to or less than 0.1290 ohms per 1000 feet |
| 304 meters). |
Current Draw | The battery plant rectifiers must be capable of providing |
| current for the System including that required for System |
| holdover and for charging the batteries. In addition, this may |
| include DC current required for an inverter that provides |
| Occupier to peripheral equipment if it is installed and for |
| future growth. |
Circuit Breaker | An Underwriter Laboratories (UL) listed and Canadian |
| Safety Association (CSA) certified circuit breaker must be |
| provided at the battery plant power board for each System |
| cabinet feeder. The recommended circuit breakers are 75 |
| ampere Airpax |
| |
Redundancy | Redundancy of the battery chargers/rectifiers should be |
| considered. This would also provide the additional current |
| necessary to recharge the batteries after being fully |
| discharged. |
Issue 1 September 1995