Install and Connect the Cabinets
1.At the DC Power Cabinet, connect a 6 AWG cable to the GROUND DISCHARGE bar. Route the cable to the port Cabinet Carrier A. Connect the cable to the
2.Repeat Step 1 for each port Cabinet Carrier A in the system.
7
1
6
8
9
5
4
2
10
3
Figure Notes:
1. | 6 AWG wire | 6. | Ground discharge bar |
2. | Ground plate | 7. | Port Cabinet D |
3. | Cabinet stack single point ground block | 8. | Port Cabinet C |
4. | To additional Port Cabinet as provided | 9. | Port Cabinet B |
5. | DC Power Cabinet | 10. | Port Cabinet A |
Figure 4-8. Ground Connection for Single-Carrier Network
Coupled Bonding Conductor (CBC)
The coupled bonding conductor (CBC) connects the cabinet