Install and Connect the Cabinets

1.At the DC Power Cabinet, connect a 6 AWG cable to the GROUND DISCHARGE bar. Route the cable to the port Cabinet Carrier A. Connect the cable to the single-point ground block in the Control Carrier (see Figure 4-7).

2.Repeat Step 1 for each port Cabinet Carrier A in the system.

7

1

6

8

9

5

4

2

10

3

Figure Notes:

1.

6 AWG wire

6.

Ground discharge bar

2.

Ground plate

7.

Port Cabinet D

3.

Cabinet stack single point ground block

8.

Port Cabinet C

4.

To additional Port Cabinet as provided

9.

Port Cabinet B

5.

DC Power Cabinet

10.

Port Cabinet A

Figure 4-8. Ground Connection for Single-Carrier Network

Coupled Bonding Conductor (CBC)

The coupled bonding conductor (CBC) connects the cabinet single-point ground block to the approved protective ground located nearest the (telephone company owned) protector block at the building entrance facility. Follow these steps to connect the coupled bonding conductor: