Install and Connect the Cabinets
Connection |
|
|
|
|
|
|
|
|
From | Cable |
|
|
|
|
|
|
|
Code | Length |
| From |
|
| To |
| |
|
|
|
|
|
|
|
|
|
|
|
| Cabinet | Position | Slot | Cabinet | Position | Slot |
|
|
|
|
|
|
|
|
|
CAD3 | 104266465 | 20 ft. | 01 | C | 02 | 02 | B | 02 |
|
|
|
|
|
|
|
|
|
CAD3 | 104266465 | 20 ft. | 01 | D | 02 | 02 | A | 01 |
|
|
|
|
|
|
|
|
|
Figure 4-12. Typical Fibre-Optic Cable Running List
In the example Running List in Figure
NOTE:
The following tasks refer to the Running List and offer typical installation instructions. If any conflict between specific details in the Running List and the instructions given in the following procedures arise, cable your system according to the Running List provided with your system.
General Rules and Recommendations for
Connecting
Although
Follow these rules and recommendations when installing
Rule 1
Do this for each connection (row) on the Running List contained in the Customer Service Document (CSD) shipped with your system. See Figure
Rule 2
Use the 9823A (shortwave) transceiver for distances of up to 4900 feet. Use the 9823B (longwave) transceiver for distances of up to 25,000 feet. Ensure all 9823As are connected to 9823As and all 9823Bs are connected to the corresponding 9823Bs.