Bosch Appliances 3.5 manual 11.4Technical data supervision-master, Physical characteristics

Models: 3.5

1 498
Download 498 pages 15.1 Kb
Page 187
Image 187
11.4Technical data supervision-master

Praesideo 3.5 Installation and User Instructions 4 Amplifiers

en 187

The loudspeakers listed in table 11.2 have a provision for a supervision-slave.

table 11.2: Loudspeakers that have provision for a supervision-slave

Speaker type

Provision for

Pre-wired, no

 

mounting

provision for

 

 

mounting

Ceiling speakers

 

 

LC1-WM06E

9

 

LC1-UM06E

9

 

LC1-UM12E

9

 

LC1-UM24E

9

 

LBC 3510/40

9

 

LBC 3520/40

9

 

LBC 3530/40

9

 

Cabinets

 

 

LBC 3011/41

9

 

LBC 3011/51

9

 

LB1-UM06E

9

 

LBC 3018/00

9

 

Columns

 

 

LBC 3210/00

9

 

LA1-UM20E

9

 

LA1-UM40E

9

 

 

 

 

Horns/Drivers

 

 

LBC 3403/16

9

 

LBC 3404/16

9

 

LBC 3405/16

9

 

LBC 3406/16

9

 

LH1-10M10E

9

 

LBC 3482/00

9

 

LBC 3483/00

9

 

LBC 3484/00

9

 

Sound projectors

 

 

LP1-BC10E

 

9

LP1-UC10E

 

9

LP1-UC20E

 

9

LBC 3432/01

9

 

LS1-OC100E

9

 

Note

The installer shall only use EN54-24 compliant loudspeakers for emergency sound systems in Europe.

11.4Technical data supervision-master

11.4.1 Physical characteristics

Dimensions (H x W x D): 60 x 50 x 17 mm Weight:

30g Connection:

20 pole flatband cable and connector Installation:

Plastic brackets for horizontal or vertical installation are delivered with the amplifier.

11.4.2 Climate conditions

Temperature:

-5 to 55 °C (operating)

-20 to 70 °C (non-operating) Relative humidity:

15 to 90%, non-condensing (operating)

5 to 95%, non-condensing (non-operating)

Air pressure: 600 to 1100 hPa

11.4.3 EMC and Safety

Electromagnetic compatibility:

EN55103-1/FCC-47 part 15B

EN55103-2

EN50121-4

EN50130-4

Electrical safety:

IEC60065 (CB-scheme)

EN60065

Approvals:

CE marking

EN60849, EN54-16 and ISO7240-16

IEC60945

11.4.4 Mean time between failure

MTBF:

50,000 hours at +55 °C

(The MTBF doubles for every 10 °C decrease in

temperature.)