47 Action programming

Praesideo 3.5 Installation and User Instructions 9 System Configuration

en 384

47 Action programming

47.1Introduction

On the Action programming pages, the keys of the keypads and the control inputs can be configured. The process of configuring a key or control input consists of two steps:

1Assigning a behavior (see section 47.2).

2 Assigning an action (see section 47.3).

47.2Behavior

47.2.1 Introduction

The behavior specifies how the control input deals with incoming signals or how the key reacts when it is pressed. The following behaviors are available:

Momentary on break or make (see section 47.2.2).

Single shot on break or make (see section 47.2.3).

Toggle on break or make (see section 47.2.4).

47.2.2 Momentary behaviors

47.2.2.1 Momentary

If the behavior is momentary, the action coupled to the control input or key is active during the time the external contact is closed.

make

break

action

figure 47.1: Momentary behavior

47.2.2.2 Momentary with immediate abort

If the behavior is momentary with immediate abort, the action coupled to the control input or key is active during the time the external contact is closed. For an example, see figure 47.2. When the external contact is opened, the action is immediately aborted.

make

break

action

start/stop

start call abort

figure 47.2: Momentary with immediate abort

47.2.2.3Momentary with phase completion and abort on repress

If the behavior is momentary with phase completion and abort on repress, the action coupled to the control input or key is active during the time the external contact is closed. For an example, see figure 47.3. When the external contact is opened, the action is stopped after the completion of the current phase

make

break

action

start/stop

start call stop

figure 47.3: Momentary with phase completion and
abort on repress (1)

When the external contact is closed again while the action is still running, the action is immediately aborted. For an example, see figure 47.4.

make

 

 

break

 

 

action

 

 

start/stop

 

 

start

call

stop abort

figure 47.4: Momentary with phase completion and

abort on repress (2)

Bosch Security Systems 2011-02

Page 384
Image 384
Bosch Appliances 3.5 manual Action programming, 47.1Introduction, 47.2Behavior, Momentary behaviors, 1: Momentary behavior