Bosch Appliances 3.5 manual Clause / Requirement 14 Design requirements

Models: 3.5

1 498
Download 498 pages 15.1 Kb
Page 65
Image 65
Clause / Requirement

Praesideo 3.5 Installation and User Instructions ISO7240-16: 2007

en 65

Clause / Requirement

14 Design requirements

14.2 Documentation

14.2.1The manufacturer shall prepare installation and user documentation, which shall be submitted to the testing authority together with the s.s.c.i.e. This shall comprise at least the following:

btechnical specifications of the inputs and outputs of the s.s.c.i.e., sufficient to permit an assessment of the mechanical, electrical, and software compatibility with other components of the system (e.g. as described in ISO 7240-1), including where relevant

3 the maximum number of alarm inputs from an emergency detection system

cinstallation information, including

1the suitability for use in various environments,

2how the requirements of 14.3.3 and 14.5.3 can be met if the s.s.c.i.e. is contained in more than one cabinet,

3how the requirements of 14.3.3 and 14.5.4 can be met if the s.s.c.i.e is designed to be used with power-supply equipment contained in a separate cabinet,

4mounting instructions, and

5instructions for connecting the inputs and outputs.

14.3.3The s.s.c.i.e. may be housed in more than one cabinet. If the documentation shows that the cabinets may be installed in locations distributed within a site, then all of the mandatory manual controls and indicators shall be on one cabinet or on cabinets declared to be suitable only for mounting adjacent to each other.

NOTE For the purposes of 14.3.3, adjacent cabinets are those that are mounted in physical contact with each other.

14.8 Indications on alphanumeric displays

14.8.2Alphanumeric displays used for mandatory

indications shall have at least one clearly distinguishable window, consisting of at least two clearly identifiable fields.

14.8.3If not included in the displayed information, the purpose of each field shall be clearly labelled.

14.8.4Where roman characters are used, a field shall be capable of containing at least the following:

aat least 16 characters where the display of a functional condition uses a cross-reference to other information to identify the location;

bat least 40 characters where the display is intended to include the complete information on the location of a functional condition.

14.8.5Where other characters are used, a field shall be capable of containing at least the following:

aat least 4 characters where the display of a functional condition uses a cross-reference to other information to identify the location;

bat least 8 characters where the display is intended to include the complete information on the location of a functional condition.

14.9 Colours of indications

14.9.1The colours of the general and specific indications from light-emitting indicators shall be as follows:

byellow for indications of

3emergency loudspeaker zones in the test state.

Compliance

Signature

The inputs and outputs for audio and control are described in the IUI, including the technical data, system functions, configuration instructions, compliancy to standards. This includes the information as requested in 14.2.1 b 3.

The IUI contains all information as requested in 14.2.1 c 1-5.

In case Praesideo is installed in multiple cabinets in locations distributed within a site, the installer must arrange that all mandatory manual controls and indicators are on the same location, either by installing them on a single cabinet or on adjacent cabinets that are mounted in physical contact with each other.

The display of the network controller is used to display mandatory indications. It consists of two separate lines of text, each representing a specific field, clearly identifiable.

Indication of the voice alarm condition is by means of the text 'Emergency' and the name of the key that activated the voice alarm condition. Indication of the fault warning condition is by means of the text 'Faults' and an indication of the number of active faults in the system. Individual faults with details are shown in a menu structure.

The display of the network controller consists of two lines with 16 characters each. It uses a menu with rotary knob navigation to select additional detailed information about functional conditions.

Not applicable, see 14.8.4.a.

Not applicable, see 14.8.4.

The test condition is an optional function and is not supported by Praesideo. See 10.

Bosch Security Systems 2011-02

Page 65
Image 65
Bosch Appliances 3.5 manual Clause / Requirement 14 Design requirements