Requirement

Compliance

Signature

eFailure of microphone, including capsule voice coil, pre-amplifier and essential wiring to the rest of the system.

fFailure of critical signal paths through the amplification chain, with individual amplifiers separately identified.

gAmplifiers or critical modules missing.

h Failure of any standby amplifier.

iFailure of emergency signal generators, including emergency pre-recorded message stores.

jFailure of any loudspeaker circuit (open- and short- circuit faults).

Compliant. Fault is indicated by a control output of the Network Controller, if properly installed. Fault is also displayed by the Network Controller and the Logging Viewer (optional).

Compliant. Fault is indicated by a control output of the Network Controller, if properly installed. Fault is also displayed by the Network Controller and the Logging Viewer (optional).

Compliant. Fault is indicated by a control output of the Network Controller, if properly installed. Fault is also displayed by the Network Controller and the Logging Viewer (optional).

Compliant. Fault is indicated by a control output of the Network Controller, if properly installed. Fault is also displayed by the Network Controller and the Logging Viewer (optional).

Compliant. Fault is indicated by a control output of the Network Controller, if properly installed. Fault is also displayed by the Network Controller and the Logging Viewer (optional). The chime generator is supervised by a watchdog circuit. First 128 MB of compact flash card (message store) is checked (first 25 minutes).

Compliant, if properly installed using single or multiple line supervision. Responsibility of the installer. Fault is indicated by a control output of the Network Controller, if properly installed. Fault is also displayed by the Network Controller and the Logging Viewer (optional).

kShort-circuit or disconnection of visual alarm devices.

Compliant, if properly installed. Responsibility of the installer. Visual alarm device must provide feedback to control input.

l

Failure of a processor to correctly execute its

Compliant, using the control outputs of the Network

 

software program.

Controller.

m

Detection of any error during memory checking.

Compliant. Program memory is checked on correctness

 

 

via checksum during system start-up. Fault is indicated

 

 

by a control output of the Network Controller, if properly

 

 

installed. Fault is also displayed by the Network

 

 

Controller and the Logging Viewer (optional).

nCessation of any scanning or interrogation process.

Compliant. Fault is indicated by a control output of the Network Controller, if properly installed. Fault is also displayed by the Network Controller and the Logging Viewer (optional).

oFailure of the interconnecting data or voice communication links between parts of a distributed system.

Compliant. Fault is indicated by a control output of the Network Controller, if properly installed. Fault is also displayed by the Network Controller and the Logging Viewer (optional).

In addition to individual fault identification at these

Compliant. Responsibility of the installer to install a

locations, a common sounder shall sound for a

buzzer and a lamp using the control outputs of the

minimum of 0,5 s every 5 s. A fault shall cause the

Network Controller. Acknowledge/Reset with Call

sounder to operate in a latched mode and a visual

Station Keypad, if properly installed or in the Logging

indicator to light, either steadily, or in a flashing mode.

Viewer.

Manual acceptance and reset switching shall be

 

included. When accepted, the sounder shall be

 

silenced and the indicator shall change to (or remain in)

 

steady illumination. The occurrence of a further fault

 

condition shall reactivate the sounder and the visual

 

indicator. When all the faults have been cleared, the

 

indicator shall be switched off, either automatically or

 

by operating a reset switch.

 

The fault indication should be given within

Compliant.

100 s of the occurrence of the fault, regardless of

 

whether the voice alarm system is being used for non-

 

emergency purposes, such as the transmission of

 

background music.

 